Ceiling Concealed Duct
Inverter
50Hz/R410A
_
5
Part 3 Design and installation
ELECTRICAL WIRING
Perform the electrical wiring work according to the electrical
wiring connection.
• All wiring must comply with local requirements.
• Select a power source that is capable of supplying
the current required by the air conditioner.
• Use a recognized circuit breaker between the
power source and the unit. A disconnection device
to adequately disconnect all supply lines must be
fitted.
• Capacity of circuit breaker recommended by
authorized personnel only
INDOOR UNIT
• Remove the control box cover for elec-
trical connection between the indoor
and outdoor unit.
• Use the cord clamper to fix the cord.
WIRING CONNECTION
Capacity Phase(Ø) Circuit Breaker
30 kBtu/h 1 25A
36 kBtu/h 1 40A
42 kBtu/h 1 40A
55 kBtu/h 1 40A
OUTDOOR UNIT
• Remove the control cover for wiring con-
nection.
• Use the cord clamper to fix the cord.
• Earthing work
- Case 1 :Terminal block of Outdoor
Unit have mark.
• Connect the cable of diameter
1.6mm
2
or more to the earthing
terminal provided in the control
box and do earthing.
- Case 2 :Terminal block of Outdoor
Unit don't have mark.
• Connect the cable of diameter
1.6mm
2
or more, to the panel of
control box, marked as and
fasten with earth screw.
❈
Please check !!
1. Installation
Outdoor
Indoor
Main
power source
Switch box
Circuit Breaker
A view
Remote
control cable
Communication
cable between
the indoor unit
and the
outdoor unit
Main PCB
Control box cover
(On which the Electric
Wiring Connection is put)
A
When connecting main power
cable, make sure the rubber
bushes are properly used in
knock-out holes after
removing the Insulation.
Insulation
Main
Terminal
Block
Cord clamp
Cord clamp