Ceiling Concealed Duct
Inverter
50Hz/R410A
_
11
Part 3 Design and installation
1. Installation
3) Group Control(Optional Wiring)
It operates maximum 16 Units by only one Wired Remote Controller,
and each Unit starts sequentially to prevent overcurrent.
• Be careful not to exchange the color of wires.
• The maximum length of connecting wire should be below 200m(25Ω) on connecting each units.
• Use a wire more than 0.5mm
2
Indoor Unit 1
Terminal(Local Supply)
Block
Terminal(Local Supply)
Block
Terminal(Local Supply)
Block
Main PCB
#1
Main PCB
#2
Main PCB
#16
Indoor Unit 2
Main PCB
Indoor Unit 16
Connector
RED(12V)
YL(SIGNAL)
BR(GND)
RED(12V)
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
Connecting Cable(Local Supply)
Connector
Connector
....
....
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
Remote Controller
<Figure 1>
Group Control
S/W GR
1
1. Master
2. Slave
2
Wired Remote
Controller
1
ON
2
3
4
5
6
7
8
Main PCB
• Set the slide switch in the wired remote contorller as "SLAVE" positon.(Figure1)
• If the main PCB is not directly connected to the wired remote controller, set the
option switch "6" in the mian PCB as "ON" position.(Figure2)