Ceiling Concealed Duct
Inverter 50Hz/R410A
_
5
Part 4 Accessories
2. Central Control Devices
Outline of system
When using a HUB, use Direct UTP Cable.
When using a HUB, use Direct UTP Cable.
• Recommended PC Specifications for AC
Manager IV
– CPU : Dual Core 2.4GHz or faster
– System Memory: 4 GB or more
– Hard Disk Space : 100 GB or more
– OS : Windows XP/7/8/8.1/10
– Resolution : 1280 x 1024 or higher
– Recommended Graphics:
VGA: For NVidia, Geforce or later.
For ATI, Radeon or later
– ACP : ACP version 1.1.4p or higher
• Max. the number of connected node* in
one RS485 Line : 32
• Communication cable
– Types : shielding wire
– Use wires of size : over 0.75 ~ 1.5 mm
2
– Max. allowable temperature of cable
: 60
– Max. length of total transmission wiring
(End to End) : 1 km
• Max. the number of connected node* in
one RS485 Line : 32
• Communication cable
– Types : shielding wire
– Use wires of size : over 0.75 ~ 1.5 mm
2
– Max. allowable temperature of cable
: 60
– Max. length of total transmission wiring
(End to End) : 1 km
• Max. the number of connected node* in
one RS485 Line : 32
• Communication cable
– Types : shielding wire
– Use wires of size : over 0.75 ~ 1.5 mm
2
– Max. allowable temperature of cable
: 60
– Max. length of total transmission wiring
(End to End) : 1 km
• * nodes : Central cont (Multi V outdoor unit x 2) + Other PI 485 G/W 32 ea
Ex) ACP 1ea + AC Smart Premium 2 ea + Multi V outdoor unit 6ea = 1 + 2 + (6 x 2) = 15 nodes
• If you need more detail, please refer to the manual of product.
(http://partner.lge.com/global : Home> Download> Manuals)
Web access
Max.length of total transmission wiring for centralized control : 1km
Remote controller
Remote controller
ACP
HUB
Ethernet
(Direct UTP Cable)
ACP
ACP
AC Manager 5
AC manager
Central control
Software
Max.length of total transmission wiring for centralized control : 1km
Remote controller
Remote controller
ACP
HUB
Ethernet
(Direct UTP Cable)
ACP
ACP
Internet web server
ACP
Max.length of total transmission wiring for centralized control : 1km
Remote controller
Remote controller
Up to 256 units by
Individual control
Ethernet
(Cross UTP Cable)
Web access
ACP BACnet
Max.length of total transmission wiring for centralized control : 1km
Remote controller
Remote controller
Up to 256 units by
Individual control
Ethernet
(Cross UTP Cable)
HUB
Building Management
System
Internet web server
ACP Lonworks
Max.length of total transmission wiring for centralized control : 1km
Remote controller
Remote controller
Up to 64 units by
Individual control
Ethernet
(Cross UTP Cable)
Building Management
System