Ceiling Concealed Duct
30
_ Inverter
50Hz/R410A
Part 2 Product Data
9. External Static Pressure & Air Flow
Note: 1. To get the desired Airflow & E.S.P combination from the table set the matching value from the table. Value other
than that in table will not give the combinations of airflow & ESP which are mentioned in the table.
2. Table is based at 230V. According to the fluctuation of voltage, air flow rate varies.
3. * : If you set the mode to 'Low E.S.P mode' on the remote controller, the unit can be operated at 60Pa without
setting the E.S.P. value.
4. Function code setting is available with PQRCVSLO / PQRCVSLOQW
Table 1
Model
Step
Air Flow
(
ℓ
/s)
Static Pressure [ Pa ]
60 *
70
80
90
100
110
120
130
140
150
160
Function code (Setting Value)
32:01
32:02
32:03
32:04
32:05
32:06
32:07
32:08
32:09
32:10
32:11
B42AWYN7G5A
High
800
81
88
92
96
97
98
100
104
105
107
107
Mid
700
77
81
88
92
93
94
96
100
101
103
103
Low
600
73
77
80
88
89
90
92
96
97
99
99
Model
Step
Air Flow
(
ℓ
/s)
Static Pressure [ Pa ]
60
70
80
90
100
120
130
140
160
180
200
Function code (Setting Value)
32:01
32:02
32:03
32:04
32:05
32:06
32:07
32:08
32:09
32:10
32:11
B55AWYN7G5A
High
1,000
94
97
100
103
106
111
113
115
120
126
129
Mid
833
87
90
92
95
98
105
106
109
116
119
124
Low
667
79
83
86
89
92
100
101
104
111
116
120
Model
Step
Air Flow
(
ℓ
/s)
Static Pressure [ Pa ]
50
60
70
90
100
120
130
140
160
180
200
Function code (Setting Value)
32:01
32:02
32:03
32:04
32:05
32:06
32:07
32:08
32:09
32:10
32:11
High
533
66
70
74
82
86
92
95
98
104
108
110
B30AWYN7G5A
Mid
433
63
67
71
79
83
89
93
95
100
105
107
Low
333
60
64
68
76
80
86
90
92
96
102
104
High
700
72
74
78
87
91
96
99
103
107
110
119
B36AWYN7G5A
Mid
600
69
71
75
83
88
93
96
99
103
107
116
Low
460
65
67
72
79
84
90
92
95
99
104
113