Display and control panel AMS 300i
44
AMS 300
i
Leuze electronic GmbH + Co. KG
Note!
The rear cover of this manual includes a fold-out page with the complete menu structure. It
describes the menu items in brief.
8.3.2
Parameter menu
Parameter handling submenu
The following functions can be called up in the
Parameter handling
submenu:
• Lock and enable parameter entry
• Set up a password
• Reset the AMS 300
i
to the default settings
Additional important information on parameter handling can be found at the end of the
chapter.
RS 422/RS 232 submenu
Table 8.1:
Parameter handling submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Parameter en
-
able
ON/OFF
The standard setting (
OFF
) prevents unintended parameter
changes.
With parameter enable activated (
ON
), the display is inverted.
In this state, it is possible to change parameters manually.
OFF
Password
Activate
password
ON/OFF
To enter a password, parameter enable must be activated.
If a password is assigned, changes to the AMS 300
i
can only
be made after the password is entered.
The master password 2301 overrides the individually set
password.
OFF
Password
entry
For setting a four-digit numerical password.
Parameters to
default
By pressing the enter button
after selecting
Parameters to default
, all parameters are reset to their standard
settings without any further security prompts.
In this case, English is selected as the display language.
Table 8.2:
RS 422/RS 232 submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Selection
RS422 / RS232
Selection of the RS 422 or RS 232 communication interface.
The interface must be connected to the bus via the M12 con
-
nection plug.
RS 422
Baud rate
19.2kbit/s / 38.4kbit/s / 57.6kbit/s / 115.2kbit/s
Selection of the serial communication baud rate. The baud
rate must be the same on the transmission and reception side
in order to enable communication.
38.4 kbit/s