Commissioning / Installation
#Leuze
#Leuze electronic
GmbH + Co KG, Postfach 11 11, D-73277 Owen/Teck, In der Braike1, D-73277 Owen/Teck, Tel. ++49 (0)7021/5730, Fax ++49 (0)7021/573199
Page 26 of 42
LZ - ELE - BA - GB - 0009 - 00
Date: 01.07.2003
Unsigned32, Read/Write
MSB
LSB
bits
31-2
1
0
value =
0 0
1
By read access the device provides information about its saving possibility.
Bit 0 = 1, the device saves parameters only on command. That means, if parameters
have been changed by the user and no "Store Parameter Command" has been
executed, at the next power on, the parameters will have there old values.
By write access the device stores the parameters to the non volatile memory.
In order to avoid storage of parameters by mistake, storage is only executed when a
specific signature is written to the object. The signature is "save".
Unsigned32
Signature MSB
LSB
e v a s
65h 76h 61h 73h
On reception of the correct signature, the device stores the parameters. If the storing
failed, the device responds with abort domain transfer, error class 6 , error code 6
(hardware fault). See also Object 6503h - Alarms.
If a wrong signature is written, the device refuses to store and responds with abort
domain transfer, error class 8, error code 0.