Display and control panel AMS 348i
49
AMS 348
i
Leuze electronic
Viewing and editing parameters
As long as parameter enabling is activated, the entire AMS 348
i
display is inverted.
As long as parameter enabling is activated, communication between control and AMS 348
i
is interrupted. The continued networking via BUS OUT is retained.
Attention!
The AMS 348
i
is deactivated on the PROFINET if parameter enabling is activated via the
display. The device is reactivated on the PROFINET after parameter enabling is exited.
Notice!
In the PROFINET network, configuration is performed exclusively via the
PROFINET Controller.
Parameters set via the display when operating the AMS 348
i
on the PROFINET are
overwritten by the parameters set in the GSD modules. For GSD modules not used actively
on the PROFINET, the default settings of the AMS apply, see
"Overview of the GSD modules"
on page 64. All parameters are thus preset by the PROFINET.
Notice!
If a password was stored, parameter enabling is not possible until this password is entered,
see "Password for parameter enabling" below.
Password for parameter enabling
Notice!
The
master password 2301
can enable the AMS 348
i
at any time.
Press the enter button to switch on parameter
enabling.
Parameter enabling
o
OFF
ON
The PWR LED illuminates orange; the display is
inverted. You can now set the individual parameters
on the display.
Press the ESC button twice to return to the
Parameter menu.
ESC
ESC