4.5.1 - Continued
4.5.1.2 - Specific parameters
Pd = 10 : skip frequencies.
Pd = 20 : preset speeds/JOG
34
Frequency inverters
FMV 2107
FMV 2307
Parameter
Description
Adjustment range
Unit
Factory setting
b14
Switching frequency and ULF
Switching frequency/ULF
b14 = 2.9/120 or 240
b14 = 5.9/120 or 240 or 480
b14 = 8.8/120 or 240 or 480
b14 = 11.7/120 or 240 or 480 or 960
kHz/Hz
2.9/120
Pc
Maximum voltage frequency
ULF/16 to ULF
Hz
50
Pd
Access to specific parameters
0, 10, 20, 30, 40, 50 or 60
-
0
* Only if b9 = 1 (controlled by the terminal block).
** Terminal C11 enables reference of terminal C5.
*** b5 is not affected by a return to factory settings.
: In all control modes (terminal block or operator panel), when the inverter is used in manual boost (b3 = 1), and
if the RUN command is maintained with a zero frequency reference, there is a D.C. injection on stopping.
These conditions must not be maintained for longer than 60 seconds in order to avoid abnormal motor
temperature rise.
Parameter
Description
Adjustment range
Unit
Factory setting
P10
Skip frequency threshold 1
P11
Skip frequency threshold 2
P0 to P1
Hz
0
P12
Skip frequency threshold 3
P13
Skip width threshold 1
P14
Skip width threshold 2
±
0.5 to
±
5.0
Hz
±
0.5
P15
Skip width threshold 3
Parameter
Description
Adjustment range
Unit
Factory setting
P20
Preset speed - 1
P21
Preset speed - 2
P22
Preset speed - 3
P23
Preset speed - 4
P0 to
±
P1
Hz
0
P24
Preset speed - 5
P25
Preset speed - 6 *
P26
Preset speed - 7 *
P27
Jog frequency
0 to 15
Hz
1.5
b20
Preset speeds/Jog
b20 = 0 : 3 JOG,
b20 = 1 : 7 speeds.
-
0
b21
b23
Standard or specific ramps.
-
-
0
0
b22
Not used
0 or 1
-
0
b24
b25
Information on terminals B1 and B2
-
0
0
b26
Disable safety cL
b26 = 0 : enabled,
b26 = 1 : disabled.
-
0
b27
Specific deceleration
b27 = 0 : Standard
b27 = 1 : Specific
-
0
b28
Enable P.I. control loop
b28 = 0 : disabled,
b28 = 1 : enabled.
-
0
b21 b23
Ramps
0
0
standard
1
0
specific
1
1
specific
0
1
specific
b24 b25
B1
B2
0
0
Freq.
Load
0
1
Load
Frequency
1
0
Load reached
Load
1
1
Load reached
Frequency
* When b28 = 1 : P25 = proportional gain, P26 = integral gain.