17
Frequency inverters
FMV 2107
FMV 2307
Terminals
Function
Type
Electrical characteristics
B5
Serial link, TX Transmission
Logic output
Non isolated outputs
0 to 5VDC,
±
60mA
B6
Serial link, TX Transmission
Logic output
High logic level (TX = +5V TX = 0V)
Low logic level (TX = 0V TX = 5V)
B7
0V common to terminals A5, A7, C1 and C6
-
0V floating
B8
B9
Selection of preset speeds
Logic input
Selection via a binary combination, (b20 = 0) of
3 preset speeds plus the reference.
B10
Inching (JOG) or extension for preset speeds
Logic input
If b20 = 0 -->
Inching (JOG),
If b20 = 1 -->
Selection via a binary combination
with B8 and B9 of 7 preset
speeds plus the reference.
C1
0V common to terminals A5, A7, B7 and C6
-
0V floating
C2
Voltage frequency reference
Analogue input
Input impedance = 94 k
Ω
- 0 to +10VDC - voltage source or
potentiometer 10 k
Ω
,
-
±
10VDC - external voltage source.
C3
Power supply for the reference, frequency
and torque potentiometers.
Analogue output
+10VDC,
±
2 %, 5mA maximum
C4
Torque reference or torque limitation
Analogue input
Input impedance = 27 k
Ω
0 to 10VDC = voltage source or 10 k
Ω
potentiometer
C5 *
Current frequency reference
Analogue input
Input impedance = 100
Ω
Current signal = 4 to 20mA, 20 to 4mA, 0 to 20mA
Enable with terminal C11, select with b11
C6
0V common to terminals A5, A7, B7 and C1
-
0V floating
C7
External trip
Logic input
0V interrupt = external trip
C8
Reset
Logic input
0V pulse = reset
C9
Ramp hold
Logic input
Connection to 0V = ramp fixed
C10
Forward operation/stop
Logic input
Connection to 0V = Forward Operation
Not connected = Stop
Terminals C10 and C12 to 0V = Stop
C11
Selection of frequency reference
Local/Remote
Logic input
Connection to 0V = Remote frequency reference
Not connected = Local frequency reference
C12
Forward operation/stop
Logic input
Connection to 0V = Reverse Operation
Not connected = Stop
Terminals C10 and C12 to 0V = Stop
Caution : in positive logic (b5 = 0) the logic inputs are enabled by the +24V.
* For the simultaneous reference of 2 inverters, the 0V must not be commons.