35
Frequency inverters
FMV 2107
FMV 2307
Pd = 30 : specific acceleration ramps
Pd = 40 : specific deceleration ramps
Pd = 50 : Selections
Pd = 60 : Read only parameters
Parameter
Description
Adjustment range
Unit
Factory setting
P30
Acceleration preset speed - 1
P31
Acceleration preset speed - 2
P32
Acceleration preset speed - 3
P33
Acceleration preset speed - 4
0.2 to 600
s
5.0
P34
Acceleration preset speed - 5
P35
Acceleration preset speed - 6
P36
Acceleration preset speed - 7
P37
Acceleration - jog
0.2 to 600
s
0.2
Parameter
Description
Adjustment range
Unit
Factory setting
P40
Deceleration preset speed - 1
P41
Deceleration preset speed - 2
P42
Deceleration preset speed - 3
P43
Deceleration preset speed - 4
0.2 to 600
s
10.0
P44
Deceleration preset speed - 5
P45
Deceleration preset speed - 6
P46
Deceleration preset speed - 7
P47
Deceleration - jog
0.2 to 600
s
0.2
Parameter
Description
Adjustment range
Unit
Factory setting
P50
Number of automatic resets
0 to 5
-
0
P51
Delay of automatic resets
1 to 5
s
1
b50
Selection of the relay function
b50 = 0 : inverter status,
b50 = 1 : minimum frequency.
-
0
b51
Enable FWD/REV key
b51 = 0 : disabled,
b51 = 1 : enabled.
-
0
b52
Catch spinning motor
b52 = 0 : disabled,
b52 = 1 : enabled.
-
0
b53
Selection of logic output A3
b53 = 0 : running,
b53 = 1 : minimum frequency.
-
0
b54
Selection : fixed or dynamic U/f characteristic.
b54 = 0 : fixed,
b54 = 1 : dynamic.
-
0
b56
Processing minor trips.
b56 = 0 : freewheel stop,
b56 = 1 : stop following ramp.
-
0
Parameter
Description
Adjustment range
Unit
Factory setting
P60
Inverter rating
151 to 753
-
See table
P61
Software version
000 to 255
-
-
P62
P63
Hour counter
000 to 255
000 to 999
-
-
P64
P65
Reserved parameters
-
-
750
0
b60
b61
b62
b63
b64
b65
Reserved parameters
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
-
0
1
0
0
1
0