16
Frequency inverters
FMV 2107
FMV 2307
3.2 - Control terminal blocks
These are located at the top of the product and above to the right.
A1
A2
Relay output
Logic ouput
+24V 100mA supply
0V
A3
A4 +24V
A5
0V
A6
A7
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
C1
C2
+10V C3
C4
C6
C5
C7
C8
C9
C10
C12
C11
PTC/PTO
0V
0V
0V
4/20mA
20/4mA
0/20mA
Frequency ref.
Torque ref.
Remote
frequency ref.
External trip
Reset
Ramp hold
Run forward
Local/Remote
Run reverse
0 to 10V
Analogue outputs
4 to 20mA
Serial link
Inverter
reception
Inverter
transmission
Preset speed 1
Preset speed 2
Preset speed 3
or jog
V
A
Terminal
Function
Type
Electrical characteristics
A1
A2
Programmable relay contacts
Relay output
240VAC - 6A resistive load
Contact closed when :
- the inverter is switched on and not tripped
(b50 = 0),
- the inverter is not faulty and the frequency is
above P0 (b50 = 1).
A3
Programmable output
Logic output
24VDC - 100 mA open collecter
Output at 0V when :
- the inverter is running (b53 = 0),
- when the frequency is at a minimum (b53 = 1).
Connect a 24VDC relay between A3 and A4.
A4
Power supply
Internal source
+24VDC,
±
10 %, 100mA
A5
0V common to terminals A7, B7, C1, C6
-
0V floating
A6
Motor probe feedback (type PTC or PTO)
If no other motor probe is used, connect A6 to
A7 (0V)
Analogue input
U output < 2.5V
Trip threshold 3 k
Ω
±
15 %
Reset threshold 1.8 k
Ω
±
15 %
A7
0V common to terminals A5, B7, C1, C6
0V floating
B1
Image proportional to the frequency
Image proportional to the load
Load reached
Analogue output
Analogue output
Logic output
Voltage : 0 to +10V if
b24 = 0
and b25 = 0
0 to +10V if
b24 = 0
and b25 = 1
0 or +10V if
b24 = 1
and b25 = 0
or b24 = 1
and b25 = 1
B2
Signal proportional to the load
Signal proportional to the frequency
Analogue output
Analogue output
Current : 4 to 20mA if b24 = 0 or 1 and b25 = 0
4 to 20mA if b24 = 0 or 1 and b25 = 1
B3
Serial link, RX reception
Logic input
Non isolated inputs
Input impedance 3.7 k
Ω
B4
Serial link RX reception
Logic input
High logic level (RX - RX > 0.2V)
Low logic level (RX - RX < -0.2V)
Note : Analogue outputs B1 and B2 are only indications and cannot be used for control.