13
Frequency inverters
FMV 2107
FMV 2307
2 - MECHANICAL INSTALLATION
2.1 - Checks on receipt
Before installing the inverter, ensure that :
- the inverter has not been damaged in transit,
- the fixing accessories are included,
- the identification plate corresponds to the power supply
and the motor.
2.2 - Installation precautions
FMV 2107 and FMV 2307 inverters must be installed in a
risk-free atmosphere, away from conductive dust,
corrosive gases and water leaks.
If this is not the case, it is recommended that they are
installed in an enclosure or a cubicle. (See section
1.4.2 for cubicle dimensions).
Mount the inverter upright, allowing 100 mm above and
below.
To prevent overheating problems, install the inverters
side by side and not on top of each other.
2.3 - Installing the inverter
2.3.1 - General
The installation is identical for the following inverters
FMV 2107 1.5M to 3.5M, FMV 2307 1.5TL to 3.5TL and
FMV 2307 1.5T to 5.5T.
Depending on the fixing accessories used, the inverter
can be installed in 3 different ways :
- on DIN rail,
- on a frame,
- cooling unit outside the cubicle.
2.3.2 - DIN rail mounting
1) Fix the DIN rail support above the cooling unit using the
M5 screw supplied.
2) Suspend the inverter on the DIN rail by inclining the top
towards the back.
3) Insert the foot mounting into the groove at the base of the
cooling unit.
4) Fix the foot mounting to the chassis using an M5 screw.
2.3.3 - Mounting on frame
1) Fix the support above the cooling unit using the M5
screw supplied.
2) Fix the inverter to the frame using 2 x M5 screws.
3) Insert the foot mounting into the groove at the base of
the cooling unit.
4) Fix the foot mounting to the frame using an M5 screw.
FMV
2107
888
M
Screw
B
C
D
E
Label
B
C
D
E
Screw
Dimensions (mm)
35
37,5
258
15
M5
FMV
2107
888
M
Screw
C
D
E
A
B
Screw
Label
A
B
C
D
E
Screw
Dimensions (mm)
16
6,5
7,5
303
15
M5