Commissioning
Configuring power supply enable input
64
EDBCSXE040 EN 6.0
6.4
Configuring power supply enable input
A HIGH level at the power supply enable input X6/DI1 enables the charging of the DC bus.
Even if the control is carried out via the system bus (CAN), the input must be set to HIGH
level to charge the DC bus.
The reaction of the power supply module to a low level or falling edge at X6/DI1 can be set
under C0468.
ƒ
C0468 can be found in the GDC parameter menu (
Digital I/O
.
Parameter
C0468
Designation
Function of power supply enable (X6/DI1)
Data type: INTEGER_32
Index: 24107
dec
= 5E2B
hex
Setting of power supply enable via terminal X6/DI1
Note:
The parameters can only be changed if the controller is inhibited.
64
Selection list
(Lenze setting printed in bold)
Information
0 Mains disconnection (slow
discharge)
1 Mains disconnection and
TRIP−RESET
2 Mains disconnection and quick
discharge (short−circuit braking)
4 Mains disconnection, quick
discharge (short−circuit braking),
and TRIP−RESET
Note!
Mains voltage dips can be reduced by decreasing the max. charging current
limit (C0022).
ƒ
C0022 can be found in the GDC parameter menu (
Short setup
.
Parameter
C0022
Designation
Max. charging current after power supply enable
Data type: INTEGER_32
Index: 24553
dec
= 5FE9
hex
Setting of the maximum charging current after power supply enable
Setting range
(min. value | unit | max. value)
Lenze setting
2.0
A
25.0
ECSxE040: 32.0
(from firmware V4.0)
16.0 A