background image

# 504,910M

Page 11

The compressor is charged with sufficient polyol
ester oil for line set lengths up to 50'. If line set
lengths longer than 50' will be required, add 1 oz. of
oil for every additional 10' of line set. Do not add any
more than 7 oz. of oil. Copeland has approved Mobil
EAL

TM

 Arctic 22CC and ICI EMKARATE

TM

 RL32CF for

use with these compressors when oil must be added
in the field.

If the system is void of refrigerant, the unit must be
returned to the warehouse for exchange. Do not install
a unit which has been delivered void of refrigerant.

The following procedure is intended as a general guide
and is for use on expansion valve systems only. For best
results, indoor temperature should be 70° – 80°F. Be sure
to monitor system pressures while charging.

1. Record outdoor ambient temperature using a digital

thermometer.

2. Attach high pressure gauge set and operate unit for

several minutes to allow system pressures to stabilize.

3. Compare stabilized pressures with those provided

below in Table 5. Minor variations in these pressures
may be expected due to differences in installations.
Significant differences could mean that the system is
not properly charged or that a problem exists with some
other component in the system. Pressures higher than
those listed indicate that the system is overcharged.
Pressures lower than those listed indicate that the
system is undercharged. A temperature/pressure chart
for R410A refrigerant is provided in Table 7 on page 12.
Verify adjusted charge using the approach method.

4. Outdoor temperature should be 60°F or above. 

For

best results, use the same digital thermometer
used to check outdoor ambient temperature to
check liquid line temperature.

 Verify the unit charge

using the approach method. The difference between

Refrigerant Charge Adjustment

* If line length is 

greater than 15 ft.

, add this amount.

If line length is 

less than 15 ft.

, remove this amount.

Table 4

t

e

S

e

n

i

L

d

i

u

q

i

L

r

e

t

e

m

a

i

D

t

s

u

j

d

a

.

t

f

5

r

e

p

.

z

O

*

t

e

s

e

n

i

l

.

t

f

5

1

m

o

r

f

.

n

i

6

1

/

5

.

t

f

5

r

e

p

.

z

o

2

.

n

i

8

/

3

.

t

f

5

r

e

p

.

z

o

3

Normal Operating Pressures*

(/–10 psig and S/–5 psig)

L = Liquid  S = Suction

Table 5

* These are typical pressures only. Indoor matchup,

indoor air quality, and indoor load will cause the
pressures to vary.

e

d

o

M

l

i

o

C

r

o

o

d

t

u

O

r

i

A

g

n

i

r

e

t

n

E

e

r

u

t

a

r

e

p

m

e

T

4

2

0

-

M

2

1

U

C

S

0

3

0

-

M

2

1

U

C

S

6

3

0

-

M

2

1

U

C

S

2

4

0

-

M

2

1

U

C

S

8

4

0

-

M

2

1

U

C

S

0

6

0

-

M

2

1

U

C

S

L

S

L

S

L

S

L

S

L

S

L

S

d

e

x

i

F

e

c

i

f

i

r

O

)

C

°

3

.

8

1

(

F

°

5

6

1

6

2

1

3

1

1

6

2

8

2

1

8

6

2

0

3

1

4

5

2

1

2

1

0

7

2

4

2

1

0

8

2

1

2

1

)

C

°

9

.

3

2

(

F

°

5

7

0

0

3

5

3

1

0

0

3

3

3

1

8

0

3

4

3

1

6

9

2

8

2

1

1

1

3

0

3

1

2

3

3

6

2

1

)

C

°

4

.

9

2

(

F

°

5

8

3

4

3

9

3

1

3

4

3

8

3

1

1

5

3

8

3

1

0

4

3

3

3

1

6

5

3

4

3

1

9

7

3

0

3

1

)

C

°

0

.

5

3

(

F

°

5

9

1

9

3

3

4

1

7

8

3

1

4

1

8

9

3

2

4

1

9

8

3

8

3

1

4

0

4

9

3

1

7

2

4

5

3

1

)

C

°

6

.

0

4

(

F

°

5

0

1

1

4

4

7

4

1

4

3

4

5

4

1

7

4

4

6

4

1

0

4

4

2

4

1

6

5

4

3

4

1

9

7

4

0

4

1

V

X

T

)

C

°

3

.

8

1

(

F

°

5

6

6

5

2

4

3

1

6

5

2

7

3

1

4

6

2

5

3

1

6

5

2

4

2

1

9

6

2

1

3

1

2

6

2

1

2

1

)

C

°

9

.

3

2

(

F

°

5

7

8

9

2

7

3

1

6

9

2

9

3

1

5

0

3

8

3

1

6

9

2

7

2

1

2

1

3

3

3

1

4

0

3

7

2

1

)

C

°

4

.

9

2

(

F

°

5

8

4

4

3

0

4

1

9

3

3

1

4

1

9

4

3

9

3

1

1

4

3

3

3

1

7

5

3

5

3

1

9

4

3

2

3

1

)

C

°

0

.

5

3

(

F

°

5

9

4

9

3

2

4

1

4

8

3

4

4

1

6

9

3

0

4

1

9

8

3

6

3

1

6

0

4

7

3

1

7

9

3

6

3

1

)

C

°

6

.

0

4

(

F

°

5

0

1

8

4

4

3

4

1

2

3

4

6

4

1

6

4

4

3

4

1

0

4

4

0

4

1

0

6

4

0

4

1

9

4

4

0

4

1

Summary of Contents for SCU12M-024

Page 1: ...on and service performed by unqualified persons can result in property damage personal injury or death WARNING Risk of electrical shock Disconnect all remote power supplies before installing or servic...

Page 2: ...A B C 4 2 0 M 2 1 U C S n i 5 2 4 1 4 2 4 1 4 2 m m 5 3 6 6 1 6 6 1 6 0 3 0 M 2 1 U C S 6 3 0 M 2 1 U C S 2 4 0 M 2 1 U C S 8 4 0 M 2 1 U C S n i 3 3 4 1 2 3 4 1 4 2 m m 8 3 8 9 1 8 6 1 6 0 6 0 M 2 1...

Page 3: ...12M condensing units use R410A which is an ozone friendly HFC refrigerant This unit must be installed with a matching indoor coil and line set SCU12M units are designed for use in expansion valve TXV...

Page 4: ...SCU12M unit Field refrigerant piping consists of liquid and suction lines from the outdoor unit sweat connections to the indoor coil flare or sweat connections Flushing Existing Line Set and Indoor C...

Page 5: ...to flow back into the low side of the sys tem Disconnect the liquid and vapor lines from the existing outdoor unit 2 Remove the existing outdoor unit Set the new R410A unit and follow the brazing conn...

Page 6: ...that all of the R22 vapor is recovered Allow the recovery to pull a vacuum on the system NOTE A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor...

Page 7: ...using 4 Connect the external equalizer line to the equalizer port on the suction line splice 5 Strap the superheat sensing bulb to the suction header If installing an expansion valve on an indoor coil...

Page 8: ...r Suction Line Service Valve 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension to turn the stem clockwise to seat the valve Tighten it firmly 3 Replace t...

Page 9: ...s Check all joints for leaks Purge nitrogen and R410A mixture Correct any leaks and recheck IMPORTANT The leak detector must be capable of sensing HFC refrigerant Evacuation Evacuating the system of n...

Page 10: ...pen both manifold valves and start vacuum pump 5 Evacuate the line set and indoor unit to an absolute pressure of 23mm 23 000 microns of mercury approximately 1 in of mercury During the early stages o...

Page 11: ...he same digital thermometer used to check outdoor ambient temperature to check liquid line temperature Verify the unit charge using the approach method The difference between Refrigerant Charge Adjust...

Page 12: ...2 p m e T F e r u s s e r P g i s P 4 7 0 4 1 2 5 7 4 7 1 2 6 7 9 0 2 2 7 7 4 4 2 2 8 7 0 8 2 2 9 7 6 1 3 2 0 8 3 5 3 2 1 8 0 9 3 2 2 8 7 2 4 2 3 8 5 6 4 2 4 8 3 0 5 2 5 8 1 4 5 2 6 8 0 8 5 2 7 8 0 2...

Page 13: ...d installer or service agency At the beginning of each cooling season the system should be checked as follows 1 Clean and inspect condenser coil Coil may be flushed with a water hose Be sure the power...

Page 14: ...Page 14 504 910M 4 Check all wiring for loose connections 5 Check for correct voltage at unit with unit operating 6 Check amp draw on blower motor Unit nameplate _________ Actual _________...

Page 15: ...504 910M Page 15 Figure 7 Connection Diagram Part 534 638W...

Page 16: ...ligation in connection with the warranted product What is NOT Covered 1 Cabinets or cabinet pieces 2 Normal maintenance items such as filters fan belts fuses or other consumable items 3 Damage caused...

Reviews: