background image

# 504,910M

Page 13

OPERATION

Outdoor unit and indoor blower cycle on demand from the
room thermostat. When the thermostat blower switch is
moved to the ON position, the indoor blower operates
continuously.

Compressor Time Delay (TD1)

A compressor time delay is used to prevent compressor
short cycling and to prevent the compressor from running
backwards. When there is demand for a cooling cycle, the
control delays compressor operation for about 5 minutes
(+ or – 2 minutes). Do not bypass the control.

High Pressure Switch

SCU12M units are equipped with a high pressure switch
that is located in the liquid line of the compressor. The
switch (SPST, manual reset, normally closed) removes
power from the compressor when discharge pressure
rises above factory setting at 640 ± 10 psi.

Filter Drier

A drier is shipped with each SCU12M unit. The drier must
be field installed in the liquid line between the liquid line
service valve and the expansion valve. 

This drier must

be installed to ensure a clean, moisture-free system.

 A

replacement drier is available through the local distributor.

Failure to install the filter drier will void the warranty.

Maintenance and service must be performed by a quali-
fied installer or service agency.

At the beginning of each cooling season, the system
should be checked as follows:

1. Clean and inspect condenser coil. Coil may be

flushed with a water hose. Be sure the power is off
before using water to clean the coil.

2. Outdoor fan motor is pre-lubricated and sealed. No

further lubrication is needed.

3. Visually inspect connecting lines and coils for evi-

dence of oil leaks.

4. Check wiring for loose connections.

5. Check for correct voltage at unit (with unit operating).

6. Check amp-draw outdoor fan motor.

Unit nameplate _________  Actual _________

NOTE – If owner complains of insufficient cooling, the
unit should be gauged and refrigerant charge
checked. Refer to the 

Charging

 section on page 10.

Indoor Coil

1. Clean coil, if necessary.

2. Check connecting lines and coils for evidence of oil

leaks.

3. Check condensate line and clean, if necessary.

Indoor Unit

1. Clean or change filters.

2. Adjust blower speed for cooling. Measure the pres-

sure drop over the coil to determine the correct blower
CFM. Refer to the unit information service manual for
pressure drop tables and procedure.

3. Belt drive blowers: Check belt for wear and proper

tension.

MAINTENANCE

Before performing maintenance operations on
system, turn the electric power to unit OFF at
disconnect switch(es). Unit may have multiple
power supplies. Electrical shock could cause
personal injury or death.

  WARNING

Summary of Contents for SCU12M-024

Page 1: ...on and service performed by unqualified persons can result in property damage personal injury or death WARNING Risk of electrical shock Disconnect all remote power supplies before installing or servic...

Page 2: ...A B C 4 2 0 M 2 1 U C S n i 5 2 4 1 4 2 4 1 4 2 m m 5 3 6 6 1 6 6 1 6 0 3 0 M 2 1 U C S 6 3 0 M 2 1 U C S 2 4 0 M 2 1 U C S 8 4 0 M 2 1 U C S n i 3 3 4 1 2 3 4 1 4 2 m m 8 3 8 9 1 8 6 1 6 0 6 0 M 2 1...

Page 3: ...12M condensing units use R410A which is an ozone friendly HFC refrigerant This unit must be installed with a matching indoor coil and line set SCU12M units are designed for use in expansion valve TXV...

Page 4: ...SCU12M unit Field refrigerant piping consists of liquid and suction lines from the outdoor unit sweat connections to the indoor coil flare or sweat connections Flushing Existing Line Set and Indoor C...

Page 5: ...to flow back into the low side of the sys tem Disconnect the liquid and vapor lines from the existing outdoor unit 2 Remove the existing outdoor unit Set the new R410A unit and follow the brazing conn...

Page 6: ...that all of the R22 vapor is recovered Allow the recovery to pull a vacuum on the system NOTE A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor...

Page 7: ...using 4 Connect the external equalizer line to the equalizer port on the suction line splice 5 Strap the superheat sensing bulb to the suction header If installing an expansion valve on an indoor coil...

Page 8: ...r Suction Line Service Valve 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension to turn the stem clockwise to seat the valve Tighten it firmly 3 Replace t...

Page 9: ...s Check all joints for leaks Purge nitrogen and R410A mixture Correct any leaks and recheck IMPORTANT The leak detector must be capable of sensing HFC refrigerant Evacuation Evacuating the system of n...

Page 10: ...pen both manifold valves and start vacuum pump 5 Evacuate the line set and indoor unit to an absolute pressure of 23mm 23 000 microns of mercury approximately 1 in of mercury During the early stages o...

Page 11: ...he same digital thermometer used to check outdoor ambient temperature to check liquid line temperature Verify the unit charge using the approach method The difference between Refrigerant Charge Adjust...

Page 12: ...2 p m e T F e r u s s e r P g i s P 4 7 0 4 1 2 5 7 4 7 1 2 6 7 9 0 2 2 7 7 4 4 2 2 8 7 0 8 2 2 9 7 6 1 3 2 0 8 3 5 3 2 1 8 0 9 3 2 2 8 7 2 4 2 3 8 5 6 4 2 4 8 3 0 5 2 5 8 1 4 5 2 6 8 0 8 5 2 7 8 0 2...

Page 13: ...d installer or service agency At the beginning of each cooling season the system should be checked as follows 1 Clean and inspect condenser coil Coil may be flushed with a water hose Be sure the power...

Page 14: ...Page 14 504 910M 4 Check all wiring for loose connections 5 Check for correct voltage at unit with unit operating 6 Check amp draw on blower motor Unit nameplate _________ Actual _________...

Page 15: ...504 910M Page 15 Figure 7 Connection Diagram Part 534 638W...

Page 16: ...ligation in connection with the warranted product What is NOT Covered 1 Cabinets or cabinet pieces 2 Normal maintenance items such as filters fan belts fuses or other consumable items 3 Damage caused...

Reviews: