background image

# 504,910M

Page 9

Leak Testing

After the line set has been connected to the indoor and
outdoor units, the line set connections and indoor unit
must be checked for leaks.

Using an Electronic Leak Detector

1. Connect the high pressure hose of the manifold

gauge set to the suction valve service port. (Normally
the high pressure hose is connected to the liquid line
port; however, connecting it to the suction ports helps
to protect the manifold gauge set from damage
caused by high pressure.)

2. With both manifold valves closed, connect the cylin-

der of R410A refrigerant. Open the valve on the
R410A cylinder (vapor only).

3. Open the high pressure side of the manifold to allow

R410A into the line set and indoor unit. Weigh in a
trace amount of R410A. (A trace amount is a maxi-
mum of 2 oz. of refrigerant or 3 lbs. pressure.) Close
the valve on the R410A cylinder and the valve on the
high pressure side of the manifold gauge set. Discon-
nect the R410A cylinder.

The ball valve is equipped with a service port with a
factory-installed Schrader valve. A service port cap
protects the Schrader valve from contamination and
serves as the primary seal.

4. Connect a cylinder of nitrogen with a pressure regulat-

ing valve to the center port of the manifold gauge set.

When using high pressure gas such as nitrogen
for this purpose, be sure to use a regulator that
can control the pressure  down to 1 or 2 psig.

5. Adjust nitrogen pressure to 150 psig. Open the valve

on the high side of the manifold gauge set to pressur-
ize the line set and the indoor coil.

6. After a short period of time, open a refrigerant port to

make sure that an adequate amount of refrigerant has
been added for detection (refrigerant requirements will
vary with lengths). Check all joints for leaks. Purge
nitrogen and R410A mixture. Correct any leaks and
recheck.

IMPORTANT: The leak detector must be capable of
sensing HFC refrigerant.

Evacuation

Evacuating the system of non-condensables is critical for
proper operation of the unit. Non-condensables are
defined as any gas that will not condense under tempera-
tures and pressures present during operation of an air
conditioning system. Non-condensables and water vapor
combine with refrigerant to produce substances that
corrode copper piping and compressor parts.

Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument that
reads from  50 microns to at least 10,000 microns.

Compliant scroll compressors (or any refrigerant
compressor) should never be used to evacuate a
refrigeration or air conditioning system.

1. Connect the manifold gauge set to the service valve

ports as follows:

Low pressure gauge to suction line service valve

High pressure gauge to liquid line service valve

2. Connect micron gauge.

3. Connect the vacuum pump (with vacuum gauge) to

the center port of the manifold gauge set.

Refrigerant can be harmful if inhaled. Refrig-
erant must always be used and recovered
responsibly. Incorrect or irresponsible use of
refrigerant can result in personal injury or
death.

  WARNING

Never use oxygen to pressurize refrigeration
or air conditioning systems. Oxygen will ex-
plode on contact with oil and could cause
personal injury or death.

  WARNING

Do not use a compressor to evacuate a system.
Avoid deep vacuum operation. Extremely low
vacuums can cause internal arcing and com-
pressor failure. Danger of equipment damage.
Damage caused by deep vacuum operation will
void warranty.

  WARNING

Do not attempt to backseat the valve. Attempts
to backseat the valve will cause snap ring to
explode from valve body under pressure of
refrigerant. Personal injury and unit damage
will result.

  WARNING

Summary of Contents for SCU12M-024

Page 1: ...on and service performed by unqualified persons can result in property damage personal injury or death WARNING Risk of electrical shock Disconnect all remote power supplies before installing or servic...

Page 2: ...A B C 4 2 0 M 2 1 U C S n i 5 2 4 1 4 2 4 1 4 2 m m 5 3 6 6 1 6 6 1 6 0 3 0 M 2 1 U C S 6 3 0 M 2 1 U C S 2 4 0 M 2 1 U C S 8 4 0 M 2 1 U C S n i 3 3 4 1 2 3 4 1 4 2 m m 8 3 8 9 1 8 6 1 6 0 6 0 M 2 1...

Page 3: ...12M condensing units use R410A which is an ozone friendly HFC refrigerant This unit must be installed with a matching indoor coil and line set SCU12M units are designed for use in expansion valve TXV...

Page 4: ...SCU12M unit Field refrigerant piping consists of liquid and suction lines from the outdoor unit sweat connections to the indoor coil flare or sweat connections Flushing Existing Line Set and Indoor C...

Page 5: ...to flow back into the low side of the sys tem Disconnect the liquid and vapor lines from the existing outdoor unit 2 Remove the existing outdoor unit Set the new R410A unit and follow the brazing conn...

Page 6: ...that all of the R22 vapor is recovered Allow the recovery to pull a vacuum on the system NOTE A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor...

Page 7: ...using 4 Connect the external equalizer line to the equalizer port on the suction line splice 5 Strap the superheat sensing bulb to the suction header If installing an expansion valve on an indoor coil...

Page 8: ...r Suction Line Service Valve 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension to turn the stem clockwise to seat the valve Tighten it firmly 3 Replace t...

Page 9: ...s Check all joints for leaks Purge nitrogen and R410A mixture Correct any leaks and recheck IMPORTANT The leak detector must be capable of sensing HFC refrigerant Evacuation Evacuating the system of n...

Page 10: ...pen both manifold valves and start vacuum pump 5 Evacuate the line set and indoor unit to an absolute pressure of 23mm 23 000 microns of mercury approximately 1 in of mercury During the early stages o...

Page 11: ...he same digital thermometer used to check outdoor ambient temperature to check liquid line temperature Verify the unit charge using the approach method The difference between Refrigerant Charge Adjust...

Page 12: ...2 p m e T F e r u s s e r P g i s P 4 7 0 4 1 2 5 7 4 7 1 2 6 7 9 0 2 2 7 7 4 4 2 2 8 7 0 8 2 2 9 7 6 1 3 2 0 8 3 5 3 2 1 8 0 9 3 2 2 8 7 2 4 2 3 8 5 6 4 2 4 8 3 0 5 2 5 8 1 4 5 2 6 8 0 8 5 2 7 8 0 2...

Page 13: ...d installer or service agency At the beginning of each cooling season the system should be checked as follows 1 Clean and inspect condenser coil Coil may be flushed with a water hose Be sure the power...

Page 14: ...Page 14 504 910M 4 Check all wiring for loose connections 5 Check for correct voltage at unit with unit operating 6 Check amp draw on blower motor Unit nameplate _________ Actual _________...

Page 15: ...504 910M Page 15 Figure 7 Connection Diagram Part 534 638W...

Page 16: ...ligation in connection with the warranted product What is NOT Covered 1 Cabinets or cabinet pieces 2 Normal maintenance items such as filters fan belts fuses or other consumable items 3 Damage caused...

Reviews: