background image

# 504,910M

Page 7

Expansion Valve Systems

Expansion valves equipped with Chatleff-type fittings are
available from the manufacturer. To install a thermo
extension valve (see Figure 4):

1. Insert suction line splice between evaporator and

suction line with the equalizer port pointing upwards.

To prevent plugging the equalizer line with oil, the
equalizer port must be between a 10:00 and 2:00
position.

2. Separate the distributor assembly and remove the

piston orifice and used teflon seal. Insert nozzle end of
the thermo expansion valve along with a new teflon seal
into the distributor and tighten to 20 – 30 ft. lbs. Use
backup wrench on all wrench flats. 

Overtightening will

crush the teflon seal and may cause a leak.

3. Attach liquid line portion of distributor assembly along

with new teflon seal to the inlet of the thermo expan-
sion valve. Tighten to 20 – 30 ft. lbs. Use backup
wrench on all wrench flats. 

Overtightening will

crush the teflon seal and may cause a leak.

Fixed Orifice Systems

SCU12M units are shipped with a fixed orifice refrigerant
metering device. Replace the existing indoor unit fixed
orifice with the orifice supplied with this unit. Place the
supplied fixed orifice sticker on the indoor cabinet after
installation. See Table 2 for the proper fixed orifice size for
each unit. In nonstandard applications, the provided fixed
orifice may not be appropriately sized.

Install the fixed orifice as shown in Figure 4. Do not twist
cap tubes when loosening the seal nut from the orifice
housing.

4. Connect the external equalizer line to the equalizer

port on the suction line splice.

5. Strap the superheat sensing bulb to the suction header.

If installing an expansion valve on an indoor coil that
previously used a fixed orifice, be sure to remove the
existing fixed orifice. Failure to remove a fixed orifice
when installing an expansion valve to the indoor coil will
result in improper operation and damage to the system.

Manifold Gauge Set

Manifold gauge sets used with systems charged with
R410A refrigerant must be capable of handling the higher
system operating pressures. The gauges should be rated
for use with pressures 0 – 800 on the high side and a low
side of 30" vacuum to 250 psi with dampened speed to
500 psi. Gauge hoses must be rated for use at up to 800
psi of pressure with a 4000 psi burst rating.

Liquid and Suction Line Service Valves

The liquid line and suction line service valves (see Figure
5 on page 8) and gauge ports are accessible from inside
the unit, behind the access panel. The service ports are
used for leak testing, evacuating, charging, and checking
charge. See Table 3 on page 8 for torque requirements.

Each valve is equipped with a service port which has a
factory-installed Schrader valve. A service port cap
protects the schrader valve from contamination and
serves as the primary leak seal.

To Access the Schrader Port:

1. Remove the access panel.

2. Remove the service port cap with an adjustable wrench.

Metering Device Installation

Figure 4

Fixed Orifice Sizes

Table 2

l

e

d

o

M

e

z

i

S

e

c

i

f

i

r

O

d

e

x

i

F

4

2

0

-

M

2

1

U

C

S

3

6

0

.

0

3

0

-

M

2

1

U

C

S

3

6

0

.

6

3

0

-

M

2

1

U

C

S

1

7

0

.

2

4

0

-

M

2

1

U

C

S

8

7

0

.

8

4

0

-

M

2

1

U

C

S

1

8

0

.

0

6

0

-

M

2

1

U

C

S

0

9

0

.

Summary of Contents for SCU12M-024

Page 1: ...on and service performed by unqualified persons can result in property damage personal injury or death WARNING Risk of electrical shock Disconnect all remote power supplies before installing or servic...

Page 2: ...A B C 4 2 0 M 2 1 U C S n i 5 2 4 1 4 2 4 1 4 2 m m 5 3 6 6 1 6 6 1 6 0 3 0 M 2 1 U C S 6 3 0 M 2 1 U C S 2 4 0 M 2 1 U C S 8 4 0 M 2 1 U C S n i 3 3 4 1 2 3 4 1 4 2 m m 8 3 8 9 1 8 6 1 6 0 6 0 M 2 1...

Page 3: ...12M condensing units use R410A which is an ozone friendly HFC refrigerant This unit must be installed with a matching indoor coil and line set SCU12M units are designed for use in expansion valve TXV...

Page 4: ...SCU12M unit Field refrigerant piping consists of liquid and suction lines from the outdoor unit sweat connections to the indoor coil flare or sweat connections Flushing Existing Line Set and Indoor C...

Page 5: ...to flow back into the low side of the sys tem Disconnect the liquid and vapor lines from the existing outdoor unit 2 Remove the existing outdoor unit Set the new R410A unit and follow the brazing conn...

Page 6: ...that all of the R22 vapor is recovered Allow the recovery to pull a vacuum on the system NOTE A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor...

Page 7: ...using 4 Connect the external equalizer line to the equalizer port on the suction line splice 5 Strap the superheat sensing bulb to the suction header If installing an expansion valve on an indoor coil...

Page 8: ...r Suction Line Service Valve 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension to turn the stem clockwise to seat the valve Tighten it firmly 3 Replace t...

Page 9: ...s Check all joints for leaks Purge nitrogen and R410A mixture Correct any leaks and recheck IMPORTANT The leak detector must be capable of sensing HFC refrigerant Evacuation Evacuating the system of n...

Page 10: ...pen both manifold valves and start vacuum pump 5 Evacuate the line set and indoor unit to an absolute pressure of 23mm 23 000 microns of mercury approximately 1 in of mercury During the early stages o...

Page 11: ...he same digital thermometer used to check outdoor ambient temperature to check liquid line temperature Verify the unit charge using the approach method The difference between Refrigerant Charge Adjust...

Page 12: ...2 p m e T F e r u s s e r P g i s P 4 7 0 4 1 2 5 7 4 7 1 2 6 7 9 0 2 2 7 7 4 4 2 2 8 7 0 8 2 2 9 7 6 1 3 2 0 8 3 5 3 2 1 8 0 9 3 2 2 8 7 2 4 2 3 8 5 6 4 2 4 8 3 0 5 2 5 8 1 4 5 2 6 8 0 8 5 2 7 8 0 2...

Page 13: ...d installer or service agency At the beginning of each cooling season the system should be checked as follows 1 Clean and inspect condenser coil Coil may be flushed with a water hose Be sure the power...

Page 14: ...Page 14 504 910M 4 Check all wiring for loose connections 5 Check for correct voltage at unit with unit operating 6 Check amp draw on blower motor Unit nameplate _________ Actual _________...

Page 15: ...504 910M Page 15 Figure 7 Connection Diagram Part 534 638W...

Page 16: ...ligation in connection with the warranted product What is NOT Covered 1 Cabinets or cabinet pieces 2 Normal maintenance items such as filters fan belts fuses or other consumable items 3 Damage caused...

Reviews: