background image

Page 6

# 504,910M

rated for use with R410A refrigerant. Wrap a wet cloth
around the valve body and the copper tube stub.
Remove light maroon washers from service valves
and shield light maroon stickers to protect them
during brazing. Braze the line set to the service valve.

4. Quench the joint with water or a wet cloth to prevent

heat damage to the valve core and opening port. 

The

tube end must stay bottomed in the fitting during
final assembly to ensure proper seating, sealing,
and rigidity.

5. Flush line set and evaporator if required (refer to

Flushing Existing Line Set and Indoor Coil 

on page

4).

6. Install the fixed orifice (supplied with unit) or R410A

approved thermal expansion valve (not supplied) in
the liquid line at the indoor coil. (See 

Refrigerant

Metering Device

 section that follows.)

7. Install the provided filter drier (approved for use with

R410A refrigerant) in the liquid line as close as
possible to the fixed orifice or expansion device. 

Do

not leave the drier uncapped for more than 10 – 15
minutes prior to brazing, evacuation, and leak
testing. Polyol ester oils used in this system
absorb moisture quickly. Failure to install the filter
drier will void the warranty.

Refrigerant Metering Device

SCU12M units are designed for use with either a fixed
orifice or an expansion valve system. See the indoor coil
installation instructions approved TXV and fixed orifice
matchups and application information. Refer to the
appropriate following section for information on installing
the chosen refrigerant metering device.

6. Invert the cylinder of clean R22 and open its valve to

allow liquid refrigerant to flow into the system through
the suction line valve. Allow the refrigerant to pass
from the cylinder and through the line set and the
indoor coil before it enters the recovery machine.

7. After all of the liquid refrigerant has been recovered,

switch the recovery machine to vapor recovery so that
all of the R22 vapor is recovered. Allow the recovery
to pull a vacuum on the system.

NOTE:

 A single system flush should remove all of the

mineral oil from the existing refrigerant lines and
indoor coil. A second flushing may be done (using
clean refrigerant) if insufficient  amounts of mineral oil
were removed during the first flush. 

Each time the

system is flushed, you must allow the recovery
machine to pull a vacuum on the system at the
end of the procedure.

8. Close the valve on the inverted R22 cylinder and the

gauge set valves. Pump the remaining refrigerant out
of the recovery machine and turn the machine off.

9. Use nitrogen to break the vacuum on the refrigerant

lines and indoor coil before removing the recovery
machine, gauges, and R22 refrigerant drum. Re-
install pressure tap valve cores into the SCU12M
service valves.

10. Install the provided orifice or expansion valve (ap-

proved for use with R410A refrigerant) in the liquid line
at the indoor coil.

Plumbing Connections Using New Indoor Coil and
Line Set

If refrigerant lines are to be routed through a wall, seal
and isolate the opening so vibration is not transmitted to
the building.

Line length should be no greater than 50'. Use Table 1 to
select line set diameters to ensure oil return to the com-
pressor.

Brazing Connection Procedure

1. The end of the refrigerant line must be cut square and

its internal shape must remain round. The line must
be free of nicks or dents and must be deburred (I.D.
and O.D.).

2. Before making line set connections, use dry nitrogen

to purge the refrigerant piping. This will help to
prevent oxidation and the introduction of moisture into
the system.

3. Use silver alloy brazing rods (5% or 6% silver alloy for

copper-to-copper brazing or 45% silver alloy for
copper-to-brass or copper-to-steel brazing) which are

Refrigerant Line Set Diameters

Table 1

l

e

d

o

M

d

i

u

q

i

L

e

n

i

L

n

o

i

t

c

u

S

e

n

i

L

4

2

0

-

M

2

1

U

C

S

0

3

0

-

M

2

1

U

C

S

6

3

0

-

M

2

1

U

C

S

.

n

i

8

/

3

)

m

m

0

1

(

.

n

i

4

/

3

)

m

m

9

1

(

2

4

0

-

M

2

1

U

C

S

8

4

0

-

M

2

1

U

C

S

.

n

i

8

/

3

)

m

m

0

1

(

.

n

i

8

/

7

)

m

m

2

2

(

0

6

0

-

M

2

1

U

C

S

.

n

i

8

/

3

)

m

m

0

1

(

.

n

i

8

/

1

-

1

)

m

m

9

2

(

Summary of Contents for SCU12M-024

Page 1: ...on and service performed by unqualified persons can result in property damage personal injury or death WARNING Risk of electrical shock Disconnect all remote power supplies before installing or servic...

Page 2: ...A B C 4 2 0 M 2 1 U C S n i 5 2 4 1 4 2 4 1 4 2 m m 5 3 6 6 1 6 6 1 6 0 3 0 M 2 1 U C S 6 3 0 M 2 1 U C S 2 4 0 M 2 1 U C S 8 4 0 M 2 1 U C S n i 3 3 4 1 2 3 4 1 4 2 m m 8 3 8 9 1 8 6 1 6 0 6 0 M 2 1...

Page 3: ...12M condensing units use R410A which is an ozone friendly HFC refrigerant This unit must be installed with a matching indoor coil and line set SCU12M units are designed for use in expansion valve TXV...

Page 4: ...SCU12M unit Field refrigerant piping consists of liquid and suction lines from the outdoor unit sweat connections to the indoor coil flare or sweat connections Flushing Existing Line Set and Indoor C...

Page 5: ...to flow back into the low side of the sys tem Disconnect the liquid and vapor lines from the existing outdoor unit 2 Remove the existing outdoor unit Set the new R410A unit and follow the brazing conn...

Page 6: ...that all of the R22 vapor is recovered Allow the recovery to pull a vacuum on the system NOTE A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor...

Page 7: ...using 4 Connect the external equalizer line to the equalizer port on the suction line splice 5 Strap the superheat sensing bulb to the suction header If installing an expansion valve on an indoor coil...

Page 8: ...r Suction Line Service Valve 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension to turn the stem clockwise to seat the valve Tighten it firmly 3 Replace t...

Page 9: ...s Check all joints for leaks Purge nitrogen and R410A mixture Correct any leaks and recheck IMPORTANT The leak detector must be capable of sensing HFC refrigerant Evacuation Evacuating the system of n...

Page 10: ...pen both manifold valves and start vacuum pump 5 Evacuate the line set and indoor unit to an absolute pressure of 23mm 23 000 microns of mercury approximately 1 in of mercury During the early stages o...

Page 11: ...he same digital thermometer used to check outdoor ambient temperature to check liquid line temperature Verify the unit charge using the approach method The difference between Refrigerant Charge Adjust...

Page 12: ...2 p m e T F e r u s s e r P g i s P 4 7 0 4 1 2 5 7 4 7 1 2 6 7 9 0 2 2 7 7 4 4 2 2 8 7 0 8 2 2 9 7 6 1 3 2 0 8 3 5 3 2 1 8 0 9 3 2 2 8 7 2 4 2 3 8 5 6 4 2 4 8 3 0 5 2 5 8 1 4 5 2 6 8 0 8 5 2 7 8 0 2...

Page 13: ...d installer or service agency At the beginning of each cooling season the system should be checked as follows 1 Clean and inspect condenser coil Coil may be flushed with a water hose Be sure the power...

Page 14: ...Page 14 504 910M 4 Check all wiring for loose connections 5 Check for correct voltage at unit with unit operating 6 Check amp draw on blower motor Unit nameplate _________ Actual _________...

Page 15: ...504 910M Page 15 Figure 7 Connection Diagram Part 534 638W...

Page 16: ...ligation in connection with the warranted product What is NOT Covered 1 Cabinets or cabinet pieces 2 Normal maintenance items such as filters fan belts fuses or other consumable items 3 Damage caused...

Reviews: