ENGLISH
APPENDIX A
ITALIANO
FRANÇAIS
ESPAÑOL
58
LXTFZ01M-IOM-1502
0
.
0
P12
Room temperature
offset (°C)
10
.
0
..
10
.
0
10
.
0
P13
Heating set-point
lower limit (°C)
5
.
0
..
35
.
0
30
.
0
P14
Heating set-point
upper limit (°C)
5
.
0
..
35
.
0
10
.
0
P15
Cooling set-point
lower limit (°C)
5
.
0
..
35
.
0
30
.
0
P16
Cooling set-point
upper limit (°C)
5
.
0
..
35
.
0
0
.
0
P17
Anti-freeze threshold
temperature (°C)
0
.
0
..
15
.
0
0
.
0
P18
Economy
reduction (°C)
0
.
0
..
10
.
0
0
.
2
P19
Room temperature
hysteresis (°C)
0
.
2
..
1
.
0
3
.
0
P20
Neutral zone
width (°C)
0
.
0
..
11
.
0
0
P21
Fan delay at
turn-on (seconds)
0
..
600
0
P22
Fan delay at
turn-off (seconds)
0
..
600
40
P23
Heating delivery
temperature threshold (°C)
0
..
99
15
P24
Cooling delivery
temperature threshold (°C)
0
..
99
0
P25
Dirty filter warning
time (x 100 hours)
0
..
50
-