background image

Page 9

KHA180, 240

3−  

3−Slide base back into original position when

finished servicing. Replace the clamp and blower
wiring in the previous location on the blower motor
base. Reconnect wiring to K3 if it was disconnected.

4− Replace retained screws on either side of the sliding

base.

5− Tighten two bolts on motor pulley side.

IMPORTANT − Align top edges of blower motor base and
mounting frame base parallel before tightening two bolts
on the other side of base. Motor shaft and blower shaft
must be parallel.

6− Tighten two bolts on other side of base.

D−Determining Unit CFM

1− The following measurements must be made with a

dry indoor coil and with air filters in place. Run blower
without a cooling demand. Measure the indoor
blower shaft RPM.

2− With all access panels in place, measure static

pressure external to unit (from supply to return).

3− Referring to page 10, use static pressure and RPM

readings to determine unit CFM. Use page 11 when
installing units with any of the optional accessories
listed.

4− The blower RPM can be adjusted at the motor pulley.

Loosen Allen screw and turn adjustable pulley
clockwise to increase CFM. Turn counterclockwise to
decrease CFM. See figure 5. Tighten Allen screw after
adjustment. Do not exceed minimum and maximum
number of pulley turns as shown in table 1.

TABLE 1

MINIMUM AND MAXIMUM PULLEY ADJUSTMENT

Belt

Minimum

Turns Open

Maximum

Turns Open

A Section

No minimum

5

B Section

1*

6

*No minimum number of turns open when B belt is used on
pulleys 6" O.D. or larger.

E−Blower Belt Adjustment

Maximum life and wear can be obtained from belts only if

proper pulley alignment and belt tension are maintained.

Tension new belts after a 

24−48

 hour period of operation.

This will allow belt to stretch and seat grooves. Make sure

blower and motor pulley are aligned as shown in figure 6.

1− Loosen four screws securing blower motor to sliding

base. See figure 5.

2−

To increase belt tension −

Turn belt tension adjusting screw to the left, or
counterclockwise, to tighten the belt. This increases
the distance between the blower motor and the
blower housing.

To loosen belt tension −

Turn the adjusting screw to the right, or clockwise to
loosen belt tension.

FIGURE 6

PULLEY ALIGNMENT

BELT

BLOWER

PULLEY

MOTOR

PULLEY

NOT ALIGNED

ALIGNED

F−Check Belt Tension

Overtensioning belts shortens belt and bearing life.
Check belt tension as follows:

1− Measure span length X. See figure 7.

MEASURE BELT TENSION

FIGURE 7

DEFLECTION 1/64" PER INCH OF SPAN

OR 1.5mm PER 100mm OF SPAN

FORCE

2− Apply perpendicular force to center of span (X) with

enough pressure to deflect belt 1/64" for every inch
of span length or 1.5mm per 100mm of span length.

Example: Deflection distance of a 40" span would be
40/64" or 5/8".

Example: Deflection distance of a 400mm span
would be 6mm.

3− Measure belt deflection force. For a used belt, the

deflection force should be 5 lbs. (35kPa) . A new belt
deflection force should be 7 lbs. (48kPa).

A force below these values indicates and
undertensioned belt. A force above these values
indicates an overtensioned belt.

G−Field−Furnished Blower Drives

For field−furnished blower drives, use pages 10 and 11 to

determine BHP and RPM required. Reference page 10 to

determine the drive number and table 2 to determine the

manufacturer’s model number.

Summary of Contents for KHA180

Page 1: ...contact with sharp edges INSTALLATION INSTRUCTIONS KHA180 15 TON KHA240 20 TON HEAT PUMP UNITS 506393 01 11 2010 Supersedes 10 2010 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Table Of Contents Di...

Page 2: ...W 711 28 711 12 3 8 314 3 1 4 83 54 1 4 1378 51 1295 90 1 8 2289 29 1 4 743 91 1 8 2315 BASE CONDENSATE DRAIN 5 3 8 137 SIDE ELECTRICAL INLETS END VIEW SIDE VIEW 129 1 2 3289 BASE 128 1 2 3264 LIFTING...

Page 3: ...tallation of KHA heat pumps must conform with standards in National Fire Protection Association NFPA Standard for Installation of Air Conditioning and Ventilating Systems NFPA No 90A Standard for Inst...

Page 4: ...completion The unit components duct system air filters and evaporator coil must be thoroughly cleaned following final construction clean up The unit operating conditions including airflow cooling oper...

Page 5: ...rotection before rigging 2 Connect rigging to the unit base using both holes in each corner See figure 2 3 All panels must be in place for rigging 4 Place field provided H style pick in place just abo...

Page 6: ...y drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys B Control Wiring 1 Route thermostat cable or wires from s...

Page 7: ...installed for loose connections Tighten as required 3 Check to ensure that refrigerant lines do not rub against the cabinet or against other refrigerant lines 4 Check voltage at disconnect switch Volt...

Page 8: ...Set thermostat or temperature control device fan switch toAUTO or ON With fan switch in ON position blower will operate continuously With fan switch in AUTO position the blower will cycle with demand...

Page 9: ...um life and wear can be obtained from belts only if proper pulley alignment and belt tension are maintained Tension new belts after a 24 48 hour period of operation This will allow belt to stretch and...

Page 10: ...6750 665 2 20 745 2 70 815 3 20 880 3 70 940 4 20 995 4 65 1045 5 10 1095 5 60 1145 6 10 1190 6 60 1235 7 10 1275 7 60 7000 675 2 35 755 2 90 825 3 40 890 3 95 950 4 45 1005 4 95 1055 5 40 1105 5 95...

Page 11: ...07 08 5000 03 05 05 07 08 5250 03 06 05 07 09 5500 03 07 05 07 10 5750 03 07 05 08 11 6000 04 08 01 05 08 11 6250 04 08 01 01 05 08 12 6500 04 09 01 02 05 08 13 6750 05 10 01 03 05 08 14 7000 05 10 0...

Page 12: ...th an economizer when outdoor air is acceptable a first stage demand will energize the economizer a second stage demand will energize compressor 1 and outdoor fans 1 2 3 Refrigerant circuits are facto...

Page 13: ...alue shown indicates an overcharge 3 The approach method is not valid for grossly over or undercharged systems Use table 3 or 4 as a guide for typical operating pressures TABLE 5 APPROACH TEMPERATURES...

Page 14: ...e unit is in the heating mode and the defrost thermostat is closed or jumpered If the timing jumper is in the TEST position at power up the defrost control will ignore the test pins When the jumper is...

Page 15: ...ry two years with a lithium base grease such as Alvania 3 Shell Oil Chevron BRB2 Standard Oil or Regal AFB2 Texas Oil Use a hand grease gun for relubrication Add only enough grease to purge through th...

Page 16: ...ions 3 Remove wire ties connecting coils slabs and separate slabs 3 4 76 102mm 4 Clean coils with detergent or commercial coil cleaner 5 Rinse thoroughly with water and reassemble 6 Secure coil slabs...

Reviews: