BLOWER DATA

BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL & AIR FILTERS IN PLACE 

FOR ALL UNITS ADD:

1 - Wet indoor coil air resistance of selected unit. 

2 - Any factory installed options air resistance (heat section, economizer, etc.) 

3 - Any field installed accessories air resistance (duct resistance, diffuser, etc.)

Then determine from blower table blower motor output and drive required. 

See page 11 for wet coil and option/accessory air resistance data.

MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT

All units require 6000 cfm minimum air with electric heat.

Air 

Volume 

cfm

TOTAL STATIC PRESSURE - In. w.g.

0.40

0.60

0.80

1.00

1.20

1.40

1.60

1.80

2.00

2.20

2.40

2.60

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

4750

575 1.10 660 1.45 740 1.80 810 2.15 870 2.50 930 2.85 985 3.20 1040 3.55 1085 3.90 1135 4.25 1180 4.65 1225 5.00

5000

585 1.25 670 1.60 750 1.95 815 2.30 880 2.70 940 3.05 995 3.40 1045 3.80 1095 4.15 1140 4.50 1185 4.90 1230 5.30

5250

595 1.35 680 1.70 755 2.10 825 2.50 890 2.90 945 3.25 1000 3.65 1050 4.00 1100 4.40 1150 4.80 1195 5.20 1235 5.60

5500

605 1.45 690 1.85 765 2.25 835 2.65 895 3.05 955 3.45 1010 3.85 1060 4.25 1110 4.70 1155 5.10 1200 5.50 1240 5.90

5750

615 1.60 700 2.00 775 2.45 840 2.85 905 3.25 960 3.65 1015 4.10 1065 4.50 1115 4.95 1160 5.35 1205 5.80 1250 6.25

6000

630 1.75 710 2.15 785 2.60 850 3.05 910 3.45 970 3.90 1025 4.35 1075 4.80 1120 5.20 1170 5.65 1215 6.10 1255 6.55

6250

640 1.90 720 2.35 795 2.80 860 3.25 920 3.70 975 4.15 1030 4.60 1080 5.05 1130 5.50 1175 5.95 1220 6.45 1265 6.90

6500

650 2.05 730 2.50 805 3.00 870 3.45 930 3.95 985 4.40 1040 4.85 1090 5.35 1140 5.85 1185 6.30 1225 6.75 1270 7.25

6750

665 2.20 745 2.70 815 3.20 880 3.70 940 4.20 995 4.65 1045 5.10 1095 5.60 1145 6.10 1190 6.60 1235 7.10 1275 7.60

7000

675 2.35 755 2.90 825 3.40 890 3.95 950 4.45 1005 4.95 1055 5.40 1105 5.95 1155 6.45 1200 6.95 1240 7.45 1285 8.00

7250

690 2.60 765 3.10 835 3.65 900 4.15 955 4.65 1015 5.25 1065 5.75 1115 6.25 1160 6.75 1205 7.30 1250 7.85 1290 8.35

7500

700 2.75 775 3.30 845 3.85 910 4.45 965 4.95 1020 5.50 1075 6.05 1125 6.60 1170 7.15 1215 7.65 1260 8.25 1300 8.75

7750

715 3.00 790 3.55 855 4.10 920 4.70 975 5.25 1030 5.80 1080 6.35 1130 6.90 1180 7.50 1225 8.05 1265 8.60 1305 9.15

8000

725 3.20 800 3.80 865 4.35 930 4.95 985 5.50 1040 6.10 1090 6.70 1140 7.25 1185 7.85 1230 8.40 1275 9.00 1315 9.60

8250

740 3.40 810 4.00 880 4.65 940 5.25 995 5.85 1050 6.45 1100 7.05 1150 7.65 1195 8.25 1240 8.85 1280 9.40 1325 10.05

8500

750 3.65 825 4.30 890 4.90 950 5.55 1005 6.15 1060 6.80 1110 7.40 1160 8.05 1205 8.65 1250 9.25 1290 9.85 1330 10.45

8750

765 3.90 835 4.55 900 5.20 960 5.85 1015 6.45 1070 7.15 1120 7.75 1165 8.35 1215 9.05 1255 9.65 1300 10.30 1340 10.90

9000

780 4.20 850 4.85 910 5.50 970 6.15 1025 6.80 1080 7.50 1130 8.15 1175 8.75 1220 9.40 1265 10.10 1310 10.80 1350 11.40

9250

790 4.45 860 5.15 925 5.85 985 6.55 1040 7.20 1090 7.85 1140 8.55 1185 9.20 1230 9.85 1275 10.55 1315 11.20 - - - - - -

9500

805 4.75 875 5.45 935 6.15 995 6.90 1050 7.60 1100 8.25 1150 8.95 1195 9.60 1240 10.30 1285 11.05 - - - - - - - - - - - -

9750

820 5.05 885 5.75 950 6.55 1005 7.20 1060 7.95 1110 8.65 1160 9.40 1205 10.05 1250 10.80 1295 11.50 - - - - - - - - - - - -

10,000 835 5.40 900 6.15 960 6.85 1015 7.60 1070 8.35 1120 9.05 1170 9.80 1215 10.50 1260 11.25 - - - - - - - - - - - - - - - - - -

10,250 845 5.65 910 6.45 970 7.20 1030 8.00 1080 8.75 1135 9.55 1180 10.25 1225 11.00 - - - - - - - - - - - - - - - - - - - - - - - -

10,500 860 6.00 925 6.85 985 7.65 1040 8.40 1095 9.20 1145 10.00 1190 10.70 1235 11.45 - - - - - - - - - - - - - - - - - - - - - - - -

10,750 875 6.40 940 7.25 1000 8.05 1055 8.85 1105 9.65 1155 10.45 1200 11.20 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

11,000 890 6.80 950 7.60 1010 8.45 1065 9.30 1115 10.05 1165 10.90 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Summary of Contents for KHA180

Page 1: ...contact with sharp edges INSTALLATION INSTRUCTIONS KHA180 15 TON KHA240 20 TON HEAT PUMP UNITS 506393 01 11 2010 Supersedes 10 2010 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Table Of Contents Di...

Page 2: ...W 711 28 711 12 3 8 314 3 1 4 83 54 1 4 1378 51 1295 90 1 8 2289 29 1 4 743 91 1 8 2315 BASE CONDENSATE DRAIN 5 3 8 137 SIDE ELECTRICAL INLETS END VIEW SIDE VIEW 129 1 2 3289 BASE 128 1 2 3264 LIFTING...

Page 3: ...tallation of KHA heat pumps must conform with standards in National Fire Protection Association NFPA Standard for Installation of Air Conditioning and Ventilating Systems NFPA No 90A Standard for Inst...

Page 4: ...completion The unit components duct system air filters and evaporator coil must be thoroughly cleaned following final construction clean up The unit operating conditions including airflow cooling oper...

Page 5: ...rotection before rigging 2 Connect rigging to the unit base using both holes in each corner See figure 2 3 All panels must be in place for rigging 4 Place field provided H style pick in place just abo...

Page 6: ...y drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys B Control Wiring 1 Route thermostat cable or wires from s...

Page 7: ...installed for loose connections Tighten as required 3 Check to ensure that refrigerant lines do not rub against the cabinet or against other refrigerant lines 4 Check voltage at disconnect switch Volt...

Page 8: ...Set thermostat or temperature control device fan switch toAUTO or ON With fan switch in ON position blower will operate continuously With fan switch in AUTO position the blower will cycle with demand...

Page 9: ...um life and wear can be obtained from belts only if proper pulley alignment and belt tension are maintained Tension new belts after a 24 48 hour period of operation This will allow belt to stretch and...

Page 10: ...6750 665 2 20 745 2 70 815 3 20 880 3 70 940 4 20 995 4 65 1045 5 10 1095 5 60 1145 6 10 1190 6 60 1235 7 10 1275 7 60 7000 675 2 35 755 2 90 825 3 40 890 3 95 950 4 45 1005 4 95 1055 5 40 1105 5 95...

Page 11: ...07 08 5000 03 05 05 07 08 5250 03 06 05 07 09 5500 03 07 05 07 10 5750 03 07 05 08 11 6000 04 08 01 05 08 11 6250 04 08 01 01 05 08 12 6500 04 09 01 02 05 08 13 6750 05 10 01 03 05 08 14 7000 05 10 0...

Page 12: ...th an economizer when outdoor air is acceptable a first stage demand will energize the economizer a second stage demand will energize compressor 1 and outdoor fans 1 2 3 Refrigerant circuits are facto...

Page 13: ...alue shown indicates an overcharge 3 The approach method is not valid for grossly over or undercharged systems Use table 3 or 4 as a guide for typical operating pressures TABLE 5 APPROACH TEMPERATURES...

Page 14: ...e unit is in the heating mode and the defrost thermostat is closed or jumpered If the timing jumper is in the TEST position at power up the defrost control will ignore the test pins When the jumper is...

Page 15: ...ry two years with a lithium base grease such as Alvania 3 Shell Oil Chevron BRB2 Standard Oil or Regal AFB2 Texas Oil Use a hand grease gun for relubrication Add only enough grease to purge through th...

Page 16: ...ions 3 Remove wire ties connecting coils slabs and separate slabs 3 4 76 102mm 4 Clean coils with detergent or commercial coil cleaner 5 Rinse thoroughly with water and reassemble 6 Secure coil slabs...

Reviews: