background image

Page 9

Diagnostic LEDs (Table 5)

The defrost board includes two LEDs used for diagnostics. The LED flashes indicate a specific diagnostic code as detailed
in the table below.

TABLE 5

LED 1

LED 2

Condition

Possible Cause(s)

Solution

OFF

OFF

Power problem

1

 No power (24V) to board terminals R &

C.

Board failure.

1

 Check control transformer power (24V).

If power is available and LED(s) are unlit,

replace board and all sensors.

ON

ON

Coil sensor problem

1

 Coil temperature outside of sensor

range.

2

 

Faulty sensor wiring connections at

board or poor sensor contact on coil.

3

 

Sensor failure.

1

 Sensor function will resume when coil

temperature is between −20°F and 110°F.

2

 

Check sensor wiring connections at

board and sensor contact on coil.

3

 

Replace board and all sensors.

OFF

ON

Ambient sensor problem

1

 Ambient temperature outside of sensor

range.

Faulty sensor wiring connections at

board or sensor.

3

 

Sensor failure.

1

 Sensor function will resume when coil

temperature is between −20°F and 110°F.

2

 

Check sensor wiring connections at

board and sensor.

Replace board and all sensors.

FLASH

FLASH

Normal operation

Unit operating normally or in standby
mode.

None required.

ON

OFF

3−Strike pressure lockout
(Short test pins or reset 24V
power to board to override
lockout)

1

 Restricted air flow over indoor or outdoor

coil.

2

 

Improper refrigerant charge.

1

 

Remove any blockages or restrictions.

Check outdoor fan motor for proper opera-
tion.

Check approach, superheat & subcooling

t

t

ON

FLASH

Low pressure switch circuit
open during Y1 demand

 

Improper refrigerant charge.

3

 

Improper metering device operation.

 

Check approach, superheat & subcooling

temperatures.

Check system pressures. Repair leaks.

Replace metering device.

FLASH

ON

High pressure switch circuit
open during Y1 demand

4

 

Poor contact between coil sensor and

coil.

Replace metering device.

4

 

Make sure that sensor is properly posi-

tioned on coil and that firm contact is es-
tablished. Refer to service manual for
proper placement.

ALTERNATING

FLASH

ALTERNATING

FLASH

5−minute delay
(Jumper test pins to override
delay)

Thermostat demand for cooling or heat
pump operation. Unit operating in 5−minute
anti−short−cycle mode.

None required.

OPERATION

The demand defrost control board initiates a defrost cycle based on either frost detection or time.

Frost Detection

 − If the compressor runs longer than 34 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds the maximum differ-

ence allowed by the control, a defrost cycle will be initiated.

IMPORTANT − The demand defrost control board will allow a greater accumulation of frost and will initiate fewer defrost cycles than a time/temperature defrost system.

Time

 − If 6 hours of heating mode compressor run time has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C), the demand defrost

control will initiate a defrost cycle.

Actuation

 − When the reversing valve is de−energized, the Y1 circuit is energized, and the coil temperature is below 35°F (2°C), the board logs the compressor run time. If

the board is not calibrated, a defrost cycle will be initiated after 34 minutes of heating mode compressor run time. The control will attempt to self−calibrate after this (and all
other) defrost cycle(s). Calibration success depends on stable system temperatures during the 20−minute calibration period. If the board fails to calibrate, another defrost
cycle will be initiated after 90 minutes of heating mode compressor run time. Once the defrost board is calibrated, it will use demand defrost logic to initiate a defrost cycle.
A demand defrost system initiates defrost when the difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control
OR after 6 hours of heating mode compressor run time has been logged since the last defrost cycle.

Termination

 − The defrost cycle ends when the coil temperature exceeds the termination temperature or after 14 minutes of defrost operation. If the defrost is terminated

by the 14−minute timer, another defrost cycle will be initiated after 34 minutes of run time.

Test Mode

 − When Y1 is energized and 24V power is being applied to the board, a test cycle can be initiated by placing the termination temperature jumper across the Test"

pins for 2 to 5 seconds. If the jumper remains across the Test" pins longer than 5 seconds, the control will ignore the test pins and revert to normal operation. The jumper
will initiate one cycle per test.

FIGURE 11

HP27−036/042 PLUMBING SHOWN

See detail A" and B"

ambient sensor
inside PVCpipe

Detail A"

−024, −030, 042

Coil Temperature

Sensor

Detail B"

−036

Summary of Contents for HP27?024

Page 1: ...22 866 22 866 22 866 22 866 Diameter in mm No of blades 24 610 3 24 610 3 24 610 3 24 610 3 C d Motor hp W 1 10 75 1 10 75 1 10 75 1 10 75 Condenser Fan Cfm L s 2800 1320 2800 1320 2800 1320 2800 132...

Page 2: ...it is in constant contact with discharge gas FIGURE 2 SCROLL FORM FIGURE 3 STATIONARY SCROLL ORBITING SCROLL DISCHARGE SUCTION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRE...

Page 3: ...ated in the unit control box for making thermostat wiring connections refer to figure 6 C Compressor Table 1 shows the specifications of compressors B1 used in HP27 series units TABLE 1 Unit Phase LRA...

Page 4: ...ee wiring diagrams for specific unit The con tactor is energized by indoor thermostat terminal Y when thermostat demand is present DANGER Electric Shock Hazard May cause injury or death Disconnect all...

Page 5: ...unit control box see figure 6 Table 3 shows the ratings of the dual ca pacitor TABLE 3 HP27 DUAL CAPACITOR RATING UNITS FAN MFD HERM MFD VAC HP27 024 4 40 370 HP27 030 4 40 370 HP27 036 4 45 370 HP27...

Page 6: ...fety Circuits The defrost control incorporates a safety circuit that allows the application of an additional pressure switch The unit s high pressure switch S4 is factory wired into this circuit See f...

Page 7: ...continuous line cycles If a system protection switch opens while the Y1 OUT cir cuit is energized the timed off control will initiate a 5 min ute delay when the pressure switch closes The timed off co...

Page 8: ...ion During normal operation the control board continuously monitors the system operation mode heating cooling the outdoor ambient temperature the outdoor coil temper ature and compressor run time to d...

Page 9: ...rol board initiates a defrost cycle based on either frost detection or time Frost Detection If the compressor runs longer than 34 minutes and the actual difference between the clear coil and frosted c...

Page 10: ...en the unit will remain in Heating Mode Remove and reapply test jumper to return to test mode if desired If sensor circuits are closed the unit will go into Defrost Mode Defrost mode ends Unit enters...

Page 11: ...on will not function again until the jumper is removed and re ap plied Time Delay The timed off delay is five minutes long The delay helps protect the compressor from short cycling in case the pow er...

Page 12: ...Use Lennox L10 flare or L15 sweat series line sets as shown in table 7 or field fabricated refrigerant lines Refer to the piping section of the Lennox Unit Information Service Manual for proper size...

Page 13: ...APOR LINE VALVE SUCTION SERVICE PORT TO HCFC 2 2 DRUM HIGH PRESSURE LIMIT THERMOME TER WELL ACCUMULATOR FIGURE 15 NOTE Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant l...

Page 14: ...LVE VALVE CLOSED VALVE FRONT SEATED FIELD SIDE UNIT SIDE To Access Schrader Port 1 Remove access panel 2 Remove service port cap with an adjustable wrench 3 Connect gauge to the service port 4 When te...

Page 15: ...uge to center port of gauge manifold With both manifold service valves open start pump and evac uate indoor coil and refrigerant lines IMPORTANT A temperature vacuum gauge mercury vacuum U tube or the...

Page 16: ...Below 60 F 16 C NOTE It may be necessary to restrict air flow in order to reach liquid pressures in the 200 250 psig range which are required for checking charge Block equal sections of air intake pa...

Page 17: ...ason the system should be cleaned as follows A Outdoor Unit 1 Clean and inspect outdoor coil Coil may be flushed with a water hose 2 Visually inspect all connecting lines joints and coils for evidence...

Page 18: ...ELD WIRING DIAGRAM HP27 WITH INDOOR UNIT 1 2 3 THERMOSTAT HEAT ANTICIPATION SET TING 4 AMP ELECTRIC HEAT WHEN TWO STAGE THERMOSTAT IS USED CONNECT SECOND STAGE HEAT BULB TO TER MINAL W2 AND REMOVE JUM...

Page 19: ...Page 19 C Diagram HP27 1 208 230 Volt 1 2 3 4 5 6 7 8...

Page 20: ...Page 20 D Diagram HP27 6 208 230 Volt 1 2 3 4 5 6 7 8...

Page 21: ...Page 21 E Diagram HP27 7 208 230 Volt 1 2 3 4 5 6 7 8...

Page 22: ...Page 22 F Diagram HP27 7 208 230 Volt 1 2 3 4 5 6 7 8...

Page 23: ...ODE 9 During heating operation when outdoor coil tempera ture drops below 35 F 2 C or 42 5 5 C see de frost system description for specific unit dash number defrost switch thermostat S6 closes 10 Defr...

Reviews: