background image

Page 5

H−Service Light Thermostat HP27

HP27−1 through −7 units are equipped with a service light
thermostat (S54) located on the compressor discharge
line. The switch is electrically connected to the service
light in the indoor thermostat.  The service light, when lit,
indicates the compressor is not running. The service light
is powered from W1 (2nd stage heat) terminal of the indoor
thermostat. The service light thermostat will close when
the discharge line falls below 110 +  5

F, indicating a prob-

lem in the system. The service light thermostat opens and
the service light goes off when discharge line reaches 130
+ 5

F indicating the compressor is running.

I−Ambient Compensating Thermistor

HP27−1 through −7 units have an ambient compensating
thermistor (RT3) mounted on the outdoor fan wiring har-
ness. The thermistor is an NTC thermistor (negative tem-
perature coefficient − increase in temperature equals de-
crease in resistance) (see figure 8). The device is con-
nected in series with the heat anticipation resistor inside the
indoor thermostat. This feature helps to prevent abnormal
droop caused by the anticipation resistors. As outdoor tem-
perature increases, the resistance across the thermistor
drops. As the resistance across the thermistor drops, the
current through the heat anticipation resistor increases.
Therefore, heat anticipation increases as outdoor tempera-
ture decreases.  Resistance at 77

F = 260 ohms + 5%; at

100

F = 150 ohms; at 32

F = 861 ohms.

FIGURE 8

AMBIENT COMPENSATING

THERMISTOR

OUTDOOR FAN, BRACKET AND

OUTDOOR FAN

FAN MOTOR

BRACKET

J−Dual Capacitor

The compressor and fan in the HP27 series units use per-
manent split capacitor motors.  A single dual capacitor
(C12) is used for both the fan motor and the compressor
(see unit wiring diagram).  The fan side of the capacitor
and the compressor side of the capacitor have different
mfd ratings. The capacitor is located inside the unit control
box (see figure 6). Table 3 shows the ratings of the dual ca-
pacitor.

TABLE 3

HP27 DUAL  CAPACITOR RATING

UNITS

FAN MFD

HERM MFD

VAC

HP27−024

4

40

370

HP27−030

4

40

370

HP27−036

4

45

370

HP27−042

4

55

370

K−Reversing Valve and Solenoid

A refrigerant reversing valve (L1) with electromechanical
solenoid is used to reverse refrigerant flow during unit op-
eration. The reversing valve is energized during cooling
demand and during defrost.

L−Defrost System HP27−1, −2, −3 and −5 units

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

CAUTION

Electrostatic discharge can affect electronic
components. Take precautions during unit
installation and service to protect the unit’s
electronic controls. Precautions will help to
avoid control exposure to electrostatic dis-
charge by putting the unit, the control and the
technician at the same electrostatic potential.
Neutralize electrostatic charge by touching
hand and all tools on an unpainted unit surface
before performing any service procedure.

The defrost system includes two components: a defrost
thermostat (S6) and a defrost control.

Defrost Thermostat

The defrost thermostat is mounted on the liquid line be-
tween the check/expansion valve and the distributor. When
defrost thermostat senses 35

F (2

C) or cooler, its con-

tacts close and send a signal to the defrost control board to
start the defrost timing. It also terminates defrost when the
liquid line warms up to 70

F (21

C).

Defrost Control

The defrost control board has the combined functions
of a time/temperature defrost control, defrost relay,
time delay, diagnostic LEDs and field connection termi-
nal strip. See figure 9.

The control provides automatic switching from normal
heating operation to defrost mode and back. During com-
pressor cycle (room thermostat demand cycle), if the O"
input is not on and the defrost thermostat is closed, the
control accumulates compressor run times at 30, 60 or 90
minute field adjustable intervals. If the defrost thermostat
remains closed when the accumulated compressor run
time ends, the defrost relay is energized and defrost be-
gins.

Summary of Contents for HP27?024

Page 1: ...22 866 22 866 22 866 22 866 Diameter in mm No of blades 24 610 3 24 610 3 24 610 3 24 610 3 C d Motor hp W 1 10 75 1 10 75 1 10 75 1 10 75 Condenser Fan Cfm L s 2800 1320 2800 1320 2800 1320 2800 132...

Page 2: ...it is in constant contact with discharge gas FIGURE 2 SCROLL FORM FIGURE 3 STATIONARY SCROLL ORBITING SCROLL DISCHARGE SUCTION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRE...

Page 3: ...ated in the unit control box for making thermostat wiring connections refer to figure 6 C Compressor Table 1 shows the specifications of compressors B1 used in HP27 series units TABLE 1 Unit Phase LRA...

Page 4: ...ee wiring diagrams for specific unit The con tactor is energized by indoor thermostat terminal Y when thermostat demand is present DANGER Electric Shock Hazard May cause injury or death Disconnect all...

Page 5: ...unit control box see figure 6 Table 3 shows the ratings of the dual ca pacitor TABLE 3 HP27 DUAL CAPACITOR RATING UNITS FAN MFD HERM MFD VAC HP27 024 4 40 370 HP27 030 4 40 370 HP27 036 4 45 370 HP27...

Page 6: ...fety Circuits The defrost control incorporates a safety circuit that allows the application of an additional pressure switch The unit s high pressure switch S4 is factory wired into this circuit See f...

Page 7: ...continuous line cycles If a system protection switch opens while the Y1 OUT cir cuit is energized the timed off control will initiate a 5 min ute delay when the pressure switch closes The timed off co...

Page 8: ...ion During normal operation the control board continuously monitors the system operation mode heating cooling the outdoor ambient temperature the outdoor coil temper ature and compressor run time to d...

Page 9: ...rol board initiates a defrost cycle based on either frost detection or time Frost Detection If the compressor runs longer than 34 minutes and the actual difference between the clear coil and frosted c...

Page 10: ...en the unit will remain in Heating Mode Remove and reapply test jumper to return to test mode if desired If sensor circuits are closed the unit will go into Defrost Mode Defrost mode ends Unit enters...

Page 11: ...on will not function again until the jumper is removed and re ap plied Time Delay The timed off delay is five minutes long The delay helps protect the compressor from short cycling in case the pow er...

Page 12: ...Use Lennox L10 flare or L15 sweat series line sets as shown in table 7 or field fabricated refrigerant lines Refer to the piping section of the Lennox Unit Information Service Manual for proper size...

Page 13: ...APOR LINE VALVE SUCTION SERVICE PORT TO HCFC 2 2 DRUM HIGH PRESSURE LIMIT THERMOME TER WELL ACCUMULATOR FIGURE 15 NOTE Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant l...

Page 14: ...LVE VALVE CLOSED VALVE FRONT SEATED FIELD SIDE UNIT SIDE To Access Schrader Port 1 Remove access panel 2 Remove service port cap with an adjustable wrench 3 Connect gauge to the service port 4 When te...

Page 15: ...uge to center port of gauge manifold With both manifold service valves open start pump and evac uate indoor coil and refrigerant lines IMPORTANT A temperature vacuum gauge mercury vacuum U tube or the...

Page 16: ...Below 60 F 16 C NOTE It may be necessary to restrict air flow in order to reach liquid pressures in the 200 250 psig range which are required for checking charge Block equal sections of air intake pa...

Page 17: ...ason the system should be cleaned as follows A Outdoor Unit 1 Clean and inspect outdoor coil Coil may be flushed with a water hose 2 Visually inspect all connecting lines joints and coils for evidence...

Page 18: ...ELD WIRING DIAGRAM HP27 WITH INDOOR UNIT 1 2 3 THERMOSTAT HEAT ANTICIPATION SET TING 4 AMP ELECTRIC HEAT WHEN TWO STAGE THERMOSTAT IS USED CONNECT SECOND STAGE HEAT BULB TO TER MINAL W2 AND REMOVE JUM...

Page 19: ...Page 19 C Diagram HP27 1 208 230 Volt 1 2 3 4 5 6 7 8...

Page 20: ...Page 20 D Diagram HP27 6 208 230 Volt 1 2 3 4 5 6 7 8...

Page 21: ...Page 21 E Diagram HP27 7 208 230 Volt 1 2 3 4 5 6 7 8...

Page 22: ...Page 22 F Diagram HP27 7 208 230 Volt 1 2 3 4 5 6 7 8...

Page 23: ...ODE 9 During heating operation when outdoor coil tempera ture drops below 35 F 2 C or 42 5 5 C see de frost system description for specific unit dash number defrost switch thermostat S6 closes 10 Defr...

Reviews: