background image

Page 15

V−CHARGING

Unit charge is based on a matching indoor coil and outdoor
coil with a 15 foot (4.5m) line set. For varying lengths of line
set, refer to table 8.

IMPORTANT

If line length is greater than 15 feet (4.5m), add
the amount of refrigerant listed in table 8 . If line
length is less than 15 feet (4.5), subtract this
amount.

Liquid Line

Set Diameter

3/8 in. (9.5 mm)

TABLE 8

Ounce per 5 foot (ml per mm) adjust from

15 ft. (4.5m)*

*If line set is greater than 15 ft. (4.5m) add this amount. If line set is less than
15 ft. (4.5m) subtract this amount

3 ounce per 5 feet (88.05g per 1.5m)

A−Leak Testing

 1 − Attach gauge manifold and connect a drum of dry ni-

trogen to center port of gauge manifold.

 2 − Add a small amount of refrigerant to the lines and coil.

Open high pressure gauge valve and pressurize line
set and indoor coil to 150 psig (1034 kPa).

WARNING

Danger  of Explosion.
Can cause injury, death and equipment
damage.
When using dry nitrogen, use a pres-
sure−reducing regulator, set at 150 pig
(1034 kPa) or less to prevent excessive
pressure.

 3 − Check lines and connections for leaks.

NOTE-If electronic leak detector is used, add a trace of re-
frigerant to nitrogen for detection by leak detector.

 4 − Release nitrogen pressure from the system, correct

any leaks and recheck.

B−Evacuating the System

Evacuating the system of non−condensables is critical for
proper operation of the unit. Non−condensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Non−condensables such as water vapor, combine
with refrigerant to produce substances that corrode copper
piping and compressor parts.

CAUTION

Danger of Equipment Damage. Avoid deep vacu-
um operation. Do not use compressors to evacu-
ate a system. Extremely low vacuums can cause
internal arcing and compressor failure. Damage
caused by deep vacuum operation will void war-
ranty.

 1− Attach gauge manifold. Connect vacuum pump (with

vacuum gauge) to center port of gauge manifold. With
both manifold service valves open, start pump and evac-
uate indoor coil and refrigerant lines.

IMPORTANT

A temperature vacuum gauge, mercury vacuum
(U−tube), or thermocouple gauge should be used.
The usual Bourdon tube gauges are not accurate
enough in the vacuum range.

 2− Evacuate  the  system  to  29  inches  (737mm)  vacuum.

During the early stages of evacuation, it is desirable to
stop the vacuum pump at least once to determine if there
is a rapid loss of vacuum. A rapid loss of vacuum would
indicate a leak in the system and a repeat of the leak test-
ing section would be necessary.

 3− After  evacuating  system  to  29  inches  (737mm),  close

gauge manifold valves to center port, stop vacuum pump
and disconnect from gauge manifold. Attach an upright
nitrogen drum to center port of gauge manifold and open
drum valve slightly to purge line at manifold. Break vacu-
um in system with nitrogen pressure by opening manifold
high pressure valve. Close manifold high pressure valve
to center port.

 4− Close nitrogen drum valve and disconnect from

gauge manifold center port. Release nitrogen pres-
sure from system.

 5− Connect vacuum pump to gauge manifold center

port. Evacuate system through manifold service
valves until vacuum in system does not rise above
.5mm of mercury absolute pressure or 500 microns
within a 20−minute period after stopping vacuum
pump.

 6− After evacuation is complete, close manifold center port,

and connect refrigerant drum. Pressurize system slight-
ly with refrigerant to break vacuum.

C−Charging

Charging must be done in the cooling mode.If system is
completely void of refrigerant, the recommended and most
accurate method of charging is to weigh the refrigerant into
the unit according to the total amount shown on the unit
nameplate. Length of refrigerant lines should be consid-
ered. See table 8 for varying line lengths.

If weighing facilities are not available or if unit is just low on
charge, the following procedure applies.

Separate discharge and vapor line service ports are pro-
vided outside the unit for connection of gauge manifold
during charging procedure as well as a suction line service
port.

Summary of Contents for HP27?024

Page 1: ...22 866 22 866 22 866 22 866 Diameter in mm No of blades 24 610 3 24 610 3 24 610 3 24 610 3 C d Motor hp W 1 10 75 1 10 75 1 10 75 1 10 75 Condenser Fan Cfm L s 2800 1320 2800 1320 2800 1320 2800 132...

Page 2: ...it is in constant contact with discharge gas FIGURE 2 SCROLL FORM FIGURE 3 STATIONARY SCROLL ORBITING SCROLL DISCHARGE SUCTION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRE...

Page 3: ...ated in the unit control box for making thermostat wiring connections refer to figure 6 C Compressor Table 1 shows the specifications of compressors B1 used in HP27 series units TABLE 1 Unit Phase LRA...

Page 4: ...ee wiring diagrams for specific unit The con tactor is energized by indoor thermostat terminal Y when thermostat demand is present DANGER Electric Shock Hazard May cause injury or death Disconnect all...

Page 5: ...unit control box see figure 6 Table 3 shows the ratings of the dual ca pacitor TABLE 3 HP27 DUAL CAPACITOR RATING UNITS FAN MFD HERM MFD VAC HP27 024 4 40 370 HP27 030 4 40 370 HP27 036 4 45 370 HP27...

Page 6: ...fety Circuits The defrost control incorporates a safety circuit that allows the application of an additional pressure switch The unit s high pressure switch S4 is factory wired into this circuit See f...

Page 7: ...continuous line cycles If a system protection switch opens while the Y1 OUT cir cuit is energized the timed off control will initiate a 5 min ute delay when the pressure switch closes The timed off co...

Page 8: ...ion During normal operation the control board continuously monitors the system operation mode heating cooling the outdoor ambient temperature the outdoor coil temper ature and compressor run time to d...

Page 9: ...rol board initiates a defrost cycle based on either frost detection or time Frost Detection If the compressor runs longer than 34 minutes and the actual difference between the clear coil and frosted c...

Page 10: ...en the unit will remain in Heating Mode Remove and reapply test jumper to return to test mode if desired If sensor circuits are closed the unit will go into Defrost Mode Defrost mode ends Unit enters...

Page 11: ...on will not function again until the jumper is removed and re ap plied Time Delay The timed off delay is five minutes long The delay helps protect the compressor from short cycling in case the pow er...

Page 12: ...Use Lennox L10 flare or L15 sweat series line sets as shown in table 7 or field fabricated refrigerant lines Refer to the piping section of the Lennox Unit Information Service Manual for proper size...

Page 13: ...APOR LINE VALVE SUCTION SERVICE PORT TO HCFC 2 2 DRUM HIGH PRESSURE LIMIT THERMOME TER WELL ACCUMULATOR FIGURE 15 NOTE Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant l...

Page 14: ...LVE VALVE CLOSED VALVE FRONT SEATED FIELD SIDE UNIT SIDE To Access Schrader Port 1 Remove access panel 2 Remove service port cap with an adjustable wrench 3 Connect gauge to the service port 4 When te...

Page 15: ...uge to center port of gauge manifold With both manifold service valves open start pump and evac uate indoor coil and refrigerant lines IMPORTANT A temperature vacuum gauge mercury vacuum U tube or the...

Page 16: ...Below 60 F 16 C NOTE It may be necessary to restrict air flow in order to reach liquid pressures in the 200 250 psig range which are required for checking charge Block equal sections of air intake pa...

Page 17: ...ason the system should be cleaned as follows A Outdoor Unit 1 Clean and inspect outdoor coil Coil may be flushed with a water hose 2 Visually inspect all connecting lines joints and coils for evidence...

Page 18: ...ELD WIRING DIAGRAM HP27 WITH INDOOR UNIT 1 2 3 THERMOSTAT HEAT ANTICIPATION SET TING 4 AMP ELECTRIC HEAT WHEN TWO STAGE THERMOSTAT IS USED CONNECT SECOND STAGE HEAT BULB TO TER MINAL W2 AND REMOVE JUM...

Page 19: ...Page 19 C Diagram HP27 1 208 230 Volt 1 2 3 4 5 6 7 8...

Page 20: ...Page 20 D Diagram HP27 6 208 230 Volt 1 2 3 4 5 6 7 8...

Page 21: ...Page 21 E Diagram HP27 7 208 230 Volt 1 2 3 4 5 6 7 8...

Page 22: ...Page 22 F Diagram HP27 7 208 230 Volt 1 2 3 4 5 6 7 8...

Page 23: ...ODE 9 During heating operation when outdoor coil tempera ture drops below 35 F 2 C or 42 5 5 C see de frost system description for specific unit dash number defrost switch thermostat S6 closes 10 Defr...

Reviews: