background image

Page 4

FIGURE 6

HP27 UNIT COMPONENTS

CONTACTOR

DEFROST CONTROL/TIMED−OFF CONTROL

LIQUID LINE

SERVICE VALVE

AND GAUGE

PORT

VAPOR LINE

SERVICE VALVE

AND GAUGE

PORT

MUFFLER

EXPANSION  VALVE

WITH 

INTERNAL CHECK

VALVE

REVERSING

VALVE

AND SOLENOID

BIFLOW FILTER/DRIER

DUAL  CAPACITOR

DISTRIBUTOR

HIGH PRESSURE

SWITCH

GROUND LUG

TERMINAL STRIP

DEFROST

THERMOSTAT

TXV

SENSING BULB −036,

−042 ONLY

SUCTION

GAUGE

PORT

THERMOMETER WELL

ACCUMULATOR

TXV

SENSING BULB 

−024, −030 ONLY

D−High Pressure Switch

An automatic reset high pressure switch (S4) located in the
liquid line of the compressor shuts off the compressor when
liquid line pressure rises above the factory setting. The switch
is normally closed and is permanently adjusted to trip (open)
at 410 + 10 psi. The switch closes at 210 + 10 psi. See figure 6
for switch location.

E−Contactor

The compressor is energized by a contactor (K1) located
in the control box. Units will use single−pole or double−pole
contactors. See wiring diagrams for specific unit. The con-
tactor is energized by indoor thermostat terminal Y when
thermostat demand is present.

DANGER

Electric Shock Hazard.
May cause injury or death.

Disconnect all remote electrical power
supplies berore opening unit panel. Unit
may have multiple power supplies.

Some units are equipped with single−
pole contactors. When unit is equipped
with a single−pole contactor, line voltage
is present at all components (even when
unit is not in operation).

F−Condenser Fan Motor

See page 1 for specifications for all condenser fan motors
(B4) used. See figure 7 if condenser fan motor replace-
ment is necessary. In all units, the condenser fan motor  is
controlled by the compressor contactor and is de−ener-
gized when the defrost relay is energized.

FIGURE 7

"A" SEE TABLE 2

FAN

 

GUARD

Condenser fan
 and motor

Wiring

Drip loop

TABLE 2

UNIT

"A" DIM.

TOLERANCE

HP27−024, −030

1 1/16"

+ 1/8"

HP27−036, −042

1 3/16"

+ 1/8"

G−Accumulator

The accumulator is located on the liquid line (see figure 6.)
The accumulator retains liquid and releases mostly vapor
to the compressor. This ensures that the liquid refrigerant
will not enter and damage the compressor.

Summary of Contents for HP27?024

Page 1: ...22 866 22 866 22 866 22 866 Diameter in mm No of blades 24 610 3 24 610 3 24 610 3 24 610 3 C d Motor hp W 1 10 75 1 10 75 1 10 75 1 10 75 Condenser Fan Cfm L s 2800 1320 2800 1320 2800 1320 2800 132...

Page 2: ...it is in constant contact with discharge gas FIGURE 2 SCROLL FORM FIGURE 3 STATIONARY SCROLL ORBITING SCROLL DISCHARGE SUCTION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRE...

Page 3: ...ated in the unit control box for making thermostat wiring connections refer to figure 6 C Compressor Table 1 shows the specifications of compressors B1 used in HP27 series units TABLE 1 Unit Phase LRA...

Page 4: ...ee wiring diagrams for specific unit The con tactor is energized by indoor thermostat terminal Y when thermostat demand is present DANGER Electric Shock Hazard May cause injury or death Disconnect all...

Page 5: ...unit control box see figure 6 Table 3 shows the ratings of the dual ca pacitor TABLE 3 HP27 DUAL CAPACITOR RATING UNITS FAN MFD HERM MFD VAC HP27 024 4 40 370 HP27 030 4 40 370 HP27 036 4 45 370 HP27...

Page 6: ...fety Circuits The defrost control incorporates a safety circuit that allows the application of an additional pressure switch The unit s high pressure switch S4 is factory wired into this circuit See f...

Page 7: ...continuous line cycles If a system protection switch opens while the Y1 OUT cir cuit is energized the timed off control will initiate a 5 min ute delay when the pressure switch closes The timed off co...

Page 8: ...ion During normal operation the control board continuously monitors the system operation mode heating cooling the outdoor ambient temperature the outdoor coil temper ature and compressor run time to d...

Page 9: ...rol board initiates a defrost cycle based on either frost detection or time Frost Detection If the compressor runs longer than 34 minutes and the actual difference between the clear coil and frosted c...

Page 10: ...en the unit will remain in Heating Mode Remove and reapply test jumper to return to test mode if desired If sensor circuits are closed the unit will go into Defrost Mode Defrost mode ends Unit enters...

Page 11: ...on will not function again until the jumper is removed and re ap plied Time Delay The timed off delay is five minutes long The delay helps protect the compressor from short cycling in case the pow er...

Page 12: ...Use Lennox L10 flare or L15 sweat series line sets as shown in table 7 or field fabricated refrigerant lines Refer to the piping section of the Lennox Unit Information Service Manual for proper size...

Page 13: ...APOR LINE VALVE SUCTION SERVICE PORT TO HCFC 2 2 DRUM HIGH PRESSURE LIMIT THERMOME TER WELL ACCUMULATOR FIGURE 15 NOTE Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant l...

Page 14: ...LVE VALVE CLOSED VALVE FRONT SEATED FIELD SIDE UNIT SIDE To Access Schrader Port 1 Remove access panel 2 Remove service port cap with an adjustable wrench 3 Connect gauge to the service port 4 When te...

Page 15: ...uge to center port of gauge manifold With both manifold service valves open start pump and evac uate indoor coil and refrigerant lines IMPORTANT A temperature vacuum gauge mercury vacuum U tube or the...

Page 16: ...Below 60 F 16 C NOTE It may be necessary to restrict air flow in order to reach liquid pressures in the 200 250 psig range which are required for checking charge Block equal sections of air intake pa...

Page 17: ...ason the system should be cleaned as follows A Outdoor Unit 1 Clean and inspect outdoor coil Coil may be flushed with a water hose 2 Visually inspect all connecting lines joints and coils for evidence...

Page 18: ...ELD WIRING DIAGRAM HP27 WITH INDOOR UNIT 1 2 3 THERMOSTAT HEAT ANTICIPATION SET TING 4 AMP ELECTRIC HEAT WHEN TWO STAGE THERMOSTAT IS USED CONNECT SECOND STAGE HEAT BULB TO TER MINAL W2 AND REMOVE JUM...

Page 19: ...Page 19 C Diagram HP27 1 208 230 Volt 1 2 3 4 5 6 7 8...

Page 20: ...Page 20 D Diagram HP27 6 208 230 Volt 1 2 3 4 5 6 7 8...

Page 21: ...Page 21 E Diagram HP27 7 208 230 Volt 1 2 3 4 5 6 7 8...

Page 22: ...Page 22 F Diagram HP27 7 208 230 Volt 1 2 3 4 5 6 7 8...

Page 23: ...ODE 9 During heating operation when outdoor coil tempera ture drops below 35 F 2 C or 42 5 5 C see de frost system description for specific unit dash number defrost switch thermostat S6 closes 10 Defr...

Reviews: