Installation and start-up of KEOR HPE UPS 200-250-300 kVA
Installation et démarrage de l’ASI KEOR HPE 200-250-300 kVA
Installazione e avviamento KEOR HPE UPS 200-250-300 kVA
32
OMP06262 REV. B
4.2
BACKFEED PROTECTION DEVICE
The KEOR HPE UPS is provided with voltage-free contacts which can be used to operate the shunt
trip coil of the external sectioning device; the external device is not part of the UPS supply and is
provided and installed at customer care.
To prevent any risk of hazardous voltage or hazardous energy present in the circuits supplying the
UPS after interruption of the input AC power , a backfeed insulating device should be installed
external to the UPS in the by pass input switchboard . This protection can be coupled with the by
pass line overcurrent protection using a MCCB equipped with a shunt trip coil and connected to
UPS applying the wiring diagram principle described in Figure 6.
In case of backfeed failure detected by the UPS , the UPS will send a signal to trip the MCCB to
isolate the UPS in order to protect the upstream distribution circuits .
The installer shall apply the following warning label on all primary power isolator that supplies the
UPS installed remote to the UPS.
The following table shows the main electrical characteristics of the external sectioning device.
Backfeed protection device
Power (kVA)
200
250
300
Maximum operating voltage (Vac)
690
690
690
Minimum rated current (A)
400
500
600
Category AC-1
AC-1
AC-1
An isolator switch with integrated undervoltage release can beinstalled inside the UPS as an option.
Before working on this circuit
-
I
solate un
i
nterrupt
i
b
l
e power system (UPS)
-
T
hen check for
hazardous
vo
l
tage between a
l
l term
i
nals
i
nclud
in
g
th
e
protective
earth
Risk of Voltage Backfedd
Summary of Contents for BSK93
Page 3: ......
Page 5: ......
Page 176: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 10 OMG38225 REV F ...
Page 278: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 112 OMG38225 REV F ...
Page 330: ......
Page 644: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 158 OMP06263 REV B ...
Page 662: ......
Page 976: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 158 OMP06263 REV B ...
Page 994: ......
Page 996: ......
Page 1235: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 10 OMW07104 REV A ...
Page 1286: ......
Page 1337: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 112 OMW07104 REV A ...
Page 1397: ...11 WWW UPS LEGRAND COM UPS CONVENTIONAL UPS ...