When the
Green Conversion
algorithm is active the rectifier operates at reduced DC voltage
and supplies the inverter alone, since the battery is disconnected from the DC bus. The battery
charge is controlled by a specific algorithm. In case no mains outage events have occurred, and
so no battery discharges have occurred too, the control logic provides to start a charging cycle
once every 25 days. The battery-charger restores the capacity lost due to the self-discharge
and remains in floating charge for additional 12 hours. As this time has elapsed the battery
static switch is opened and the battery is disconnected from the DC bus.
In case a discharge event occurs, the control logic provides to calculate the capacity which has
been lost during the discharge; as the mains is restored a charging cycle is started, which is
extended for an additional time that depends on the percentage of lost capacity, referred to the
rated value.
Lost capacity < 10%
Additional charge for
12 hours
Lost capacity between 10% and 20%
Additional charge for
48 hours
Lost capacity > 20%
Additional charge for
96 hours
Such values complies with the recommendations of the main battery manufacturers.
Set the right battery capacity
The UPS front panel allows the setting of the battery parameters, including the rated
capacity. Considering the importance that such value assumes for the correct
execution of the charge control algorithm, it is highly recommended to verify the
correctness of the programmed value.
3.3.3 Bypass
operation
The load can be switched to bypass either automatically or manually. The manual changeover
is due to the BYPASS SWITCH which forces the load to bypass. In case of failure of the bypass
line, the load is switched back to inverter without interruption.
Picture 4 – Load supplied by bypass
3.3.4 Battery
operation
In case of power failure or rectifier fault, the battery feeds the inverter without interruption. The
battery voltage drops based on the amplitude of the discharging current. The voltage drop has
no effect on the output voltage, which is kept constant by changing the PWM modulation. An
alarm is activated when the battery is near the minimum discharge value.
In case the supply is restored before the battery is completely discharged, the system will be
switched back to normal operation automatically. In the opposite case, the inverter shuts down
Summary of Contents for BSK93
Page 3: ......
Page 5: ......
Page 176: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 10 OMG38225 REV F ...
Page 278: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 112 OMG38225 REV F ...
Page 330: ......
Page 644: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 158 OMP06263 REV B ...
Page 662: ......
Page 976: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 158 OMP06263 REV B ...
Page 994: ......
Page 996: ......
Page 1235: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 10 OMW07104 REV A ...
Page 1286: ......
Page 1337: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 112 OMW07104 REV A ...
Page 1397: ...11 WWW UPS LEGRAND COM UPS CONVENTIONAL UPS ...