GENERAL UPS DESCRIPTION
3.1
TYPOLOGY
The UPS described in this manual is on-line, double conversion; the inverter included in the UPS always
supplies energy to the load, whether mains is available or not (according to the battery autonomy time).
This configuration guarantees the best service to the User, as it supplies clean power uninterruptedly,
ensuring voltage and frequency stabilization at nominal value. Thanks to the double conversion, it makes
the load completely immune from micro-interruptions and from excessive mains variations, and prevents
damage to critical loads (Computer - Instrumentation - Scientific equipment etc.).
Output voltage present
The line connected to the UPS output is energized even during mains failure, therefore in
compliance with the prescriptions of IEC EN62040-1, the installer will have to identify the
line or the plugs supplied by the UPS making the User aware of this fact.
Picture 1 – Block diagram
The UPS uses IGBT technology with a high switching frequency in order to allow a low distortion of the
current re-injected into the supply line, as well as high quality and stability of output voltage. The
components used assure high reliability, very high efficiency and maintenance easiness.
3.2
SYSTEM DESCRIPTION
3.2.1 Rectifier
It converts the three-phase voltage of the AC mains into continuous DC voltage.
It uses a three-phase fully-controlled IGBT bridge with a low harmonic absorption.
The rectifier in normal operation can operate with phase rotation clockwise and counterclockwise.
The control electronics uses a 32 bit
μ
P of latest generation that allows to reduce the distortion of the
current absorbed by mains (THDi) to less than 3%. This ensures that the rectifier does not distort the
supply mains, with regard to the other loads. It also avoids cable overheating due to the harmonics
circulation.
The rectifier is so sized as to supply the inverter at full load and the battery at the maximum charging
current.
Summary of Contents for BSK93
Page 3: ......
Page 5: ......
Page 176: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 10 OMG38225 REV F ...
Page 278: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 112 OMG38225 REV F ...
Page 330: ......
Page 644: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 158 OMP06263 REV B ...
Page 662: ......
Page 976: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 158 OMP06263 REV B ...
Page 994: ......
Page 996: ......
Page 1235: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 10 OMW07104 REV A ...
Page 1286: ......
Page 1337: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 112 OMW07104 REV A ...
Page 1397: ...11 WWW UPS LEGRAND COM UPS CONVENTIONAL UPS ...