PF 1 6K/10K Online UPS 

 
 
 
 
 
 
 
 
 
 

Uninterruptible Power Supply System 

Version:  1.1 

User Manual 

Содержание Galleon One 10K

Страница 1: ...PF 1 6K 10K Online UPS Uninterruptible Power Supply System Version 1 1 User Manual...

Страница 2: ...instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety info...

Страница 3: ...2 4 UPS INSTALLATION FOR PARALLEL SYSTEM 6 2 5 SOFTWARE INSTALLATION 7 3 OPERATIONS 8 3 1 BUTTON OPERATION 8 3 2 LED INDICATORS AND LCD PANEL 8 3 3 AUDIBLE ALARM 9 3 4 SINGLE UPS OPERATION 10 3 5 PAR...

Страница 4: ...nect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not b...

Страница 5: ...s where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use thi...

Страница 6: ...mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 6 Standards Safety IEC EN 62040 1 EMI Condu...

Страница 7: ...share current cable only available for parallel model One battery cable option NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged during transportation...

Страница 8: ...6K 6KL should be able to withstand over 40A current It is recommended to use 10AWG or thicker wire for safety and efficiency NOTE 2 The cable for 10K 10KL should be able to withstand over 63A current...

Страница 9: ...ultaneously The connection with wrong battery voltage may cause permanent damage of the UPS Make sure the voltage of the battery pack is correct Pay highly attention to the polarity marking on externa...

Страница 10: ...ing wiring diagram Diagram 1 Power cable connection Diagram2 Wiring diagram of parallel system 2 5 Software Installation For optimal computer system protection install UPS monitoring software to fully...

Страница 11: ...button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press t...

Страница 12: ...ge information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 In...

Страница 13: ...r to AC mode If the utility power is abnormal the UPS will operate in Battery mode without interruption NOTE When the UPS is running out battery it will shut down automatically at Battery mode When th...

Страница 14: ...n Users could switch off some non critical loads to disable the shutdown alarm and prolong the backup time If there is no more load to be switched off at that time you have to shut down all loads as s...

Страница 15: ...the error is fixed Please refer to section 3 3 for the details 3 4 11 Operation in Fault mode 1 When Fault LED illuminates and the buzzer beeps continuously it means that there is a fatal error in th...

Страница 16: ...input breaker and switch off the battery breaker only available for long run model 4 Remove the cabinet cover and disconnect battery wire for standard model Then modify the jumpers on the charger boar...

Страница 17: ...es are connected correctly Then Turn on another UPS A few seconds later the UPS will enter to battery mode and add to the parallel system 4 If you have the third UPS follow the same procedure of 3 The...

Страница 18: ...inverter make sure that all unit s maintenance switch at the same position When parallel system is turned on to work through inverter please do not operate the maintenance switch of any unit 3 6 Abbre...

Страница 19: ...ved Reserved for future 11 Reserved Reserved for future 12 Hot standby function enable disable Y Y Y Y Y Y 13 Battery voltage adjustment Y Y Y Y Y Y 14 Charger voltage adjustment Y Y Y Y Y Y 15 Invert...

Страница 20: ...lected in parameter 2 UPS will transfer to battery mode when input frequency is not within 56 64 Hz If Parameter 2 is ATO the Parameter 2 will show the current frequency Note If the UPS is set to CVCF...

Страница 21: ...default value is 54 0Hz 64 0Hz 05 ECO mode enable disable Interface Setting Parameter 2 Enable or disable ECO function You may choose following two options DIS disable ECO function ENA enable ECO fun...

Страница 22: ...0Hz 08 Bypass mode setting Interface Setting After it shows 08 in parameter 1 please press Enter key first Then you have the following options to choose in parameter 1 OP Bypass allowed When selected...

Страница 23: ...nd it will restart after AC recovery even without battery connected NO Hot standby function is disabled The UPS is running at normal mode and can t restart without battery 13 Battery voltage adjustmen...

Страница 24: ...battery specifications 15 Inverter voltage adjustment Interface Setting After it shows 15 in parameter 1 please press Enter key first Then you may choose Ad or SU to adjust inverter voltage in parame...

Страница 25: ...assigned numbers may be changed dynamically in the operation Operating mode status AC mode Description When the input voltage is within acceptable range UPS will provide pure and stable AC power to ou...

Страница 26: ...mode LCD display Battery mode Description When the input voltage is beyond the acceptable range or power failure UPS will backup power from battery and alarm will beep every 4 seconds LCD display Bypa...

Страница 27: ...art failure 01 None Battery SCR short circuited 21 None Bus over 02 None Inverter relay short circuited 24 None Bus under 03 None Charger short circuited 2a None Bus unbalance 04 None Can communicatio...

Страница 28: ...ry second Battery unconnected Beeping every second 3 11 Warning Code Warning code Warning event Warning code Warning event 01 Battery unconnected 10 L1 IP fuse broken 07 Over charge 21 Line situations...

Страница 29: ...move excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becomes...

Страница 30: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Страница 31: ...on applications 12 V 9 Ah Depending on applications Numbers 16 16 20 16 16 20 Recharge Time 7 hours recover to 90 capacity According to external battery pack 9 hours recover to 90 capacity According t...