34 / 137
Proline Kryomats
Ammonia (NH
3
)
Not permissible
Iron (Fe), dissolved
< 0.2 mg/L
Manganese (Mn), dissolved
< 0.05 mg/L
Aluminum (Al), dissolved
< 0.2 mg/L
Free aggressive carbonic acid (CO
2
)
Not permissible
Hydrogen sulfide (H
2
S)
Not permissible
Algae growth
Not permissible
Suspended matter
Not permissible
Risk to the environment due to oil contamination of the cooling water circuit
With a leaky condenser there is the danger that refrigerating machine oil from the coolant circuit of the cooling
thermostat can pass into the cooling water.
Follow all the legal requirements and the regulations of the water supply utility, which apply at the point of use.
Water pollution due to leakage
To avoid pollution due to a leak in the cooling water system it is recommended that a leakage-water detector
with a water cut-off is installed.
Servicing intervals
Follow the information for cleaning and decalcifying the cooling water circuit (
c)
Hoses
Elastomer hoses
Hose type
Internal width Ø mm Temperature range °C
Field of application
Order number
EPDM hose
uninsulated
12
10 – 90
For all heat transfer liquids
except mineral oils
RKJ 112
EPDM hose
insulated
12
External Ø.
approx. 35mm
-35 – 90
LZS 021
Silicone hose
uninsulated
11
10 – 100
Water,
Glycol/water mixture
RKJ 059
Silicone hose
insulated
11
External Ø.
approx. 35mm
-60 – 100
LZS 007
EPDM hose is not suitable for mineral oils.
With silicone rubber, silicone oils lead to substantial swelling
never use silicone oil with
silicone hoses.
Secure hoses against slippage with hose clips.