Error handling
77/84
D000044352 en g – E230 Residential Electricity Meter – ZxR100xC/ZMR100xR – User Manual
© Gyr
Display
Description
If error is persistent
If error is transitional
Related
event
log #
00004000 Power-fail
data
failed
checksum.
Meter operation may be
compromised. Billing
based on energy
registers after the error
occurrence is not
reliable. Error will only
occur during the power-
up sequence. This error
is set, if the checksum of
the power-fail data is
incorrect during power-
up.
Clear Error Register
F.F.0 on display and
readout by “Reset Error
Register” (W2 C150)
command using
.MAP110 or by power-
cycle.
N/A
00002000 Calibration
value failed
checksum.
Meter operation may be
compromised. Billing
based on energy
registers after the error
occurrence is not
reliable. Error will only
occur during the power-
up sequence. This error
is set, if the checksum of
the calibration data is
incorrect during power-
up.
Clear Error Register
F.F.0 on display and
readout by “Reset Error
Register” (W2 C150)
command using
.MAP110 or by power-
cycle.
N/A
00001000
UNUSED
00000800
UNUSED
00000400
UNUSED
00000200
UNUSED
00000100
UNUSED
00000008 Error
in
Parameter Data.
Meter operation may be
compromised due to
incorrect or corrupt
parameterisation.
Clear Error Register
F.F.0 on display and
readout by “Reset Error
Register” (W2 C150)
command using
.MAP110 or by power-
cycle.
N/A
00000040
UNUSED