Introduction
© Gyr
D000044352 en g – E230 Residential Electricity Meter – ZxR100xC/ZMR100xR – User Manual
CS Interface
Type Serial
bi-directional
Standard
IEC 61107 / DIN 66258
Rated Voltage
24V DC
Max. Voltage
30V DC
Transmitter Current – On state
Min.11 mA
Typ. 20 mA
Max. 30 mA
Off State
Max. 2.5 mA
Receiver Current – On state
Min. 9 mA
Typ. 20 mA
Max. 30 mA
Off State
3 mA Max.
Communication Speed
300 to 4800 Baud
RS485 Interface (ZMR100xR only)
Type Half-duplex
Standard
ANSI TIA/EIA-485-A and ISO
8482:1993
Nominal Voltage Range
-7 V to +12 V DC
Binary 1 State
Difference voltage > 0.2 V
Binary 0 State
Difference voltage < -0.2 V
Communication Speed
300 to 9600 Baud
Maximum Number of Nodes
31
Maximum Length
1000 m cable (daisy chain)
Insulation
4 kV AC/50 Hz, 1 min
Creepage Distance
6.2 mm
Impulse Voltage Withstand
6 kV peak 1.2/50
μ
s
Protocols IEC62056-21
C
Pulse Output r53
Type
S0 Interface (or data stream)
Standard
IEC 62053-31
Configurable
Imp/Wh or imp/VArh
Pulse Constant
Configurable (1 – 1000)
Supply Voltage (typ.)
24 V
Supply Voltage (max.)
50 V
Current
10 mA DC
Pulse Length
Configurable (10 ms – 1000 ms)
Maximum Line Length
1000 m