Installation and commissioning
© Gyr
D000044352 en g – E230 Residential Electricity Meter – ZxR100xC/ZMR100xR – User Manual
5.3
Mounting the meter
The connecting conductors should not be live during installation of the
meter. Electrically live parts are a life threatening hazard. Preliminary
fuses should be removed and kept in a safe place, where they cannot be
replaced by anyone unnoticed, until all work is complete.
Mount the meter as follows:
1. Find the correct and suitable position to mount the meter.
2. With suitable test equipment, check that the proposed conductors
are live. If they are live, remove the preliminary fuses and keep in a
safe place where no-one can replace unnoticed until after the work
is complete.
3. Mark the fixing points in accordance with the diagram below.
150 mm
75 mm
13
0 m
m
Sta
n
da
rd Fixing
180 mm Short
Fi
xi
ng
230 mm Extended Fixing
Figure 13. Drilling diagram for fixing screws
4. Drill the holes for the fixing screws
5. Unscrew and remove the meter terminal cover
6. Fix the meter to the meter board or other supplied surface with the
fixing screws