Table 2. Determining OBIS code for energy registers
1st digit Significance 2nd digit Significance
3rd digit Significance
1 A+
2 Max
demand
1 Tariff
1
2 A-
8
Cumulative
energy
2 Tariff
2
3 R+
9 Periodic 3 Tariff
3
4 R-
4 Tariff
4
5 Tariff
5
6 Tariff
6
For example: OBIS code 2.8.1 means A-, cumulative energy, tariff 1.
6.1.3 Energy efficiency meter displays (ZMR100xC only)
If configured appropriately, the display can list 6 new (Software
≥
K76)
items intended to allow the consumer to easily monitor energy
consumption:
Item
Display
Content
Remarks
EDL21 Total Active Power
(Summation)
P
Total Active Power
(Summation)
None
Import Energy Meter
E
Import Energy 1.8.0
Resettable
Export Energy Meter
E-E
Export Energy 2.8.0
Resettable
24 Hour Energy
Consumption
1 d
Import Energy 1.8.0
over last 24 h
Refresh
every 5 min
1 Week Energy
Consumption
7 d
Import Energy 1.8.0
over last week
Refresh
every 1 hour
1 Month Energy
Consumption
30 d
Import Energy 1.8.0
over last month
Refresh
every 1 hour
The resolution of these 6 displays is 1 W.
30 d and P registers are available in firmware version K76 or newer.
As a built-in privacy feature, if any EDL21 display is shown in
conjunction with no display button activity (presses) for 120 seconds, the
meter exits the EDL displays and returns to the Main Display list.
6.1.4 Meter
powered
with
zero energy being consumed (anti-creep mode)
Example A shows that the meter is powered on all 3 phases (L1-L2-L3),
the internal battery is in maximum charge state (4 bars) (optional
feature) and that the current register being displayed is a kWh register.
In a reverse phase situation (e.g. L1-L3-L2), the phase power segments
will flash.