Operation
51/84
D000044352 en g – E230 Residential Electricity Meter – ZxR100xC/ZMR100xR – User Manual
© Gyr
Event
no.
Name
Description
Trigger
Event Anti-
fraud
Perma-
nent
trigger
(confi-
gurable)
40 Parameter
changed
Indicates that one or more
parameters have been
changed by an external tool.
The event is triggered by the
tool.
X
45 Error
Register
Cleared
Indicates that the error register
(F.F.0) has been cleared.
X
49, 50,
51
Missing
voltage L1,
L2, L3
Indicates that the
corresponding voltage dropped
below 20 V and remained
below 20 V for a period of time
defined by parameterisation.
X X
55 Magnet
detection
Indicates that the meter has
been influenced by a strong
magnet (>0.5T). If event 55 is
recorded without event 134, a
tamper/fraud attempt has been
made, but energy
measurement has not been
affected.
X X
66 Date/time
invalid
Error X
76 Time
base
error
Error X
89 Start-up
sequence
invalid
Error X
133 Terminal
cover
removal
Indicates that the terminal
cover has been removed.
X X
134 Strong
DC
field
Indicates that the energy
measurement ICs have been
affected by the presence of a
strong DC magnet. Energy
measurement must be treated
as though it has been
tampered with, which may
result in inaccurate energy
measurements from the point
of detection.
X X
135 Front
cover
removal
Indicates that the front cover
has been removed.
X X