Start Concurrent Measurement and Request - CRC aCC!
Same command as
aC!
but in addition to the generated data the sensor returns a 3-digit checksum. For information
on how the CRC checksum gets generated, please consult ‘SDI-12 Standard Version1.3, 2012, chapter 4.4.12’.
Syntax:
Command
Answer
aCC!
a00306<CR><LF>
a
– Sensor address
a
– Sensor address
C
– Command ‘Start Concurrent
003
– Seconds the sensor needs until the
Measurement’
measured data can be returned
C
– Request for transmission of the
(= 3 s)
CRC checksum
06
– Number of provided measured data
!
– End of command
<CR><LF>
– End of answer
Example:
Command Answer
2CC!
200306<CR><LF>
Send Data - aD0! and aD1!
Data generated by the commands
C
,
M
, or
V
are requested from the sensor with
aD0!
and
aD1!
. The sensor
uses the respective arithmetic sign (’+’ or ‘-’) to separate the values. If the data was requested with a
CC
or
MC
command, it will be returned with the CRC checksum. For information on how the CRC checksum gets
generated, please consult ‘SDI-12 Standard Version1.3, 2012, chapter 4.4.12’.
The measured data is returned in metric units.
Measured data
Unit
Buffer 0
Precipitation intensity within the last minute
mm/min
Precipitation intensity within the last minute in mm/h
mm/h
Precipitation intensity since last request
mm/min
Measured data
Unit
Buffer 1
Precipitation intensity since last request in mm/h
mm/h
Precipitation amount since last request
mm/m²
Precipitation amount total
mm/m²
Syntax for measurements with aC! or aM!
Command
Answer
aD0!
a<values<CR><LF>
a
– Sensor address
a
– Sensor address
D
– Command ‘Send Data’
<values>
– Requested data separated by
0
– Request for the data in buffer 0
resp. sign (‘+’ or ‘-’)
or
1
= buffer 1
!
– End of command
<CR><LF>
– End of answer
31