11.5.1 Special Case of Precipitation
Except for the amount of precipitation, all measured values are to be read in as instantaneous values. The amount
of precipitation must be read in as a total amount. And the difference to the previous call must be formed for the
displayed and the precipitation quantity to be stored.
Note: The value overflow of the precipitation sum must be considered when calculating the difference.
The value overflow occurs at 60,000 g of collected liquid. This results in a value overflow at 3,000 mm for
sensors with a collecting surface of 200 cm
2
and a value overflow at 1,500 mm for sensors with a collecting
surface of 400 cm
2
.
11.6
Descriptive Sensor Parameter Registers (Holding Register)
Register
Parameter name
Quantity of registers Remark
Access type
40050
Device identification number
(15 characters)
8 (2 characters in
each register)
The returned data are
in form of a 16 byte
null terminated string
Read only
40100
Serial number
(11 characters)
6 (2 characters in
each register)
The returned data are
in form of a 12 byte
null terminated string
Read only
40150
Firmware version
(up to 25 characters)
13 (2 characters in
each register)
The returned data are
in form of a 26 byte
null terminated string
Read only
Example:
Retrieve the device identification number
(The identification number shown in the example is sensor-dependent. It is only used here for demonstration
purposes).
ASCII
05 03 9C 72 00 08 CB C3 05 03 10
30 30 2E 31 36
00.16480.000130
34 38 30 2E 30 30 30 31 33 30 00
37 CA
LEN
6
Transmission
Query =>
Source
Master
Dest
Slave 5
Function
Read Holding Register (3)
Func Desk
Address=40050, Quantity of Register=8
Checksum
OK:C3CB
LEN
19
Transmission
Response <=
Source
Slave 5
Dest
Master
Function
Read Holding Register (3)
Func Desk
Byte count=16
Data
30 30 2E 31 36 34 38 30 2E 30 30 30 31 33 30 00
Checksum
OK:CA37
41