Page 29

7.

When there is a call for heat, the pump and the

blower will start, the display will show the

supply temperature. The appliance will attempt

to ignite three times, if ignition is not successful,

the appliance will lock out and display “LO”.

Ignition reset is done by pressing the reset button

on top of the control panel. EBP models will

continue to operate until the 20 gallon transfer

tank is up to temperature.

8.

EBP only: Turn on a hot water tap. This puts the

appliance in the DHW mode.

 Caution

Should any pronounced odor of gas be detected, or
if the gas burner does not appear to be functioning
in a normal manner, close main shutoff valve, do
not shut off switch, and contact your heating
contractor, gas company, or factory representative.

You MUST check flame monitoring control

(ignition system safety shut-off device).
9.

Close gas shutoff valve with burner operating.

10. The gas valve status light will go out, and

immediately a new trial for ignition will begin.

The burner will not relight, because the gas is

off. The control will make two more attempts to

light the burner. Ignition will not occur, as the

gas is off. The boiler will lockout, and the

display will show “LO” after the gas valve has

closed on the third ignition attempt. The ignition

control LED will show a three-flash sequence.

11. Open gas shutoff valve. Press reset button on the

top of the control panel. The ignition sequence

will start again and the burner will start. The

appliance will return to its previous mode of

operation.

SECTION 8.
Maintenance and Component
Description

Figure 34 shows the location of the control panel

components. The parts sections show the other

components on the Endurance.

8.1 Unit Pump

The unit pump operates whenever there is a call

for heat or hot water.

It is a wetted-rotor type pump and should always

be filled with water when it is operating so that it will

cool properly.

If a pump change is required for any reason,

valve off the boiler and drain approximately 1 or 2

gallons (approx. 4-8L) of water from it. Turn off the

main disconnect switch and unplug the pump wires,

remove the pump motor. The pump housing need not

be removed. The replacement pump motor should be

installed in the reverse order from which the old pump

motor was removed. After filling the system be sure

the combustion chamber coil vents through the air vent

located on top of the boiler chamber (inlet manifold

extension).

8.2 Gas Valve

The gas valve is a 24VDC solenoid operated,

negative pressure regulated ratio valve. The outlet

pressure may be adjusted as described in the service

section. It is designed to operate with supply pressures

of 4-13 inches w.c. (1.0 to 3.2 kPa). To remove the gas

valve, shut off 120 volt power and the gas shutoff

valve, remove the 4 screws on the upper and lower

flanges and disconnect the wires from the gas valve,

the valve may now be removed. After the valve has

been removed, replace with a new valve in the reverse

order in which the old valve was removed. Turn on gas

shutoff valve and 120 volt power and check boiler

operation and gas tightness of gas valve connections.

8.3 Safety Limit Switch

The Safety Limit Switch is an automatic reset

switch with a fixed set point of 230°F (110°C). To

replace the switch, shut off the 120 volt power.

Disconnect the 2 wires from the quick connects at the

switch and remove the switch. To replace, perform the

same operations in reverse. Turn on disconnect switch

and check boiler.

8.4 Boiler Control

The Endurances uses an FX05 boiler control.

The control takes inputs from a domestic hot water

flow switch, an overheat thermostat (safety high

limit), external space heating switch, and temperature

sensors throughout the Endurance unit. Using these

signals, it works with the ignition control to ensure

proper and safe operation of the Endurance. It controls

call for heat, the modulating point for the blower, the

Endurance pump, and the signals that are sent to the

ignition control.

Figure 34. Control Panel.

Summary of Contents for EBP0110

Page 1: ...llation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or ope...

Page 2: ...elay 24 6 4 4 Oar Outdoor Reset 24 6 4 5 Oal Minimum Outdoor Reset Point 25 6 4 6 rc Outdoor Reset Ratio 25 6 4 7 oTo Warm Outdoor Shutdown 25 6 4 8 unl Temperature Units 25 6 4 9 Add Control Address...

Page 3: ...with the gas to the burner flame holder Both the intake air and the gas are metered through separate orifices before entering the combustion air blower The blower forces the air fuel mixture through t...

Page 4: ...rain etc during appliance operation or service circulator replacement control replacement etc 1 5 Clearances The dimension and criteria in Table 1 should be followed when choosing the location for the...

Page 5: ...ate the opening centerline 16 1 2 42cm above grade use optional concentric vent terminal extension part number 2400 428 shown in Figure 7 In the U S vent terminals must be at least 3 feet 0 9m above a...

Page 6: ...rements are from the centerlineof the venting to the boiler top or face of outside wall Dimensions shown in inches Configuration 2 Maximum horizontal 38 Maximum vertical 16 Measurements are from the c...

Page 7: ...Endurance Page 7 Figure 7 Concentric Vent Parts Dimensions shown in inches...

Page 8: ...tlet See note 4 3 feet 91 cm J Clearance to nonmechanical air supply Direct Vent Only 12 inches 30 cm inlet to building or the combustion air inlet Other Than Direct Vent 4 feet 1 2 m below or 36 inch...

Page 9: ...atFab Inc under the trade name of Saf T Vent by Z Flex under the trade name of Z Vent and by ProTech Systems Inc under the trade name FasNSeal Follow the special gas vent manufacturer s instructions r...

Page 10: ...Page 10 LAARS Heating Systems Figure 13 3 Vent Parts Dimensions shown in inches...

Page 11: ...r boilers that are getting all of their combustion air from inside the building The confined space shall be provided with two permanent openings communicating directly with other spaces of sufficient...

Page 12: ...reen can be used One portion of this assembly connects to the 5 air collar with a screen for the combustion air and the other part connects to the 3 flue opening see Figure 14 The rest of the 3 vent s...

Page 13: ...ocal requirements 3 Install drip leg ground joint union and drip cap to trap sediment and for test gauge access 4 Support all piping with proper hangers 5 All threaded joints should be coated with pip...

Page 14: ...e domestic potable water temperature has fallen below 39 4 C If this condition is recognized the Endurance pump will run for 5 minutes or until the boiler water temperature reaches 45 F 7 C If the boi...

Page 15: ...Endurance Page 15 Figure 19 Hydronic Piping EDP EBP with Zone Valves Figure 20 Piping Single EDP EBP Boiler for Multiple Temperature Systems Figure 21 Piping Model EDP EDN for Radiant Floor...

Page 16: ...Install an air purger in flow supply line as shown in piping diagrams 5 Install automatic float type air vent on air scoops Figure 22 Hydronic Piping EBP EDP for Systems Zoned with Circulators Figure...

Page 17: ...ipped with a Low Temperature control feature that recognizes when the water temperature at the outlet of the boiler has fallen below 39 F 4 C If this condition is recognized the Endurance pump will ru...

Page 18: ...y hand B BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS D...

Page 19: ...s il n y a pas d odeur de gaz pr s du plancher car le gaz est plus lourd que l air et peut se d poser sur le plancher QUE FAIRE EN CAS D ODEUR DE GAZ N essayez pas d allumer n importe quelque apparei...

Page 20: ...tch Neutral leg to white wire Ground wire can be connected to the grounding screw in the box or on the switch 2 For single zone installations If external pump is required e g because of large system p...

Page 21: ...Clock Thermostats That Require 24 VAC RELAY 24 VOLT NO CONTACT LAARS P N 2400 060 TO T T BOILER CONNECTIONS 120V 24 20VA W Y G R Rc L1 HOT L2 120 VAC TRANSFORMER NOTE This wiring required only for sin...

Page 22: ...rner On Point that is calculated by subtracting the Burner On Differential from the Burner Control Point The Burner On Differential is adjustable from 4 to 30 F 2 to 17 C in the EDP EDN models and is...

Page 23: ...ic Example Figure 32 EDP EDN Flow Schematic 6 Calculated Setpoint for Outdoor Reset shown as CSP when used The temperature that the controller has calculated for a setpoint based on the outdoor temper...

Page 24: ...This parameter shown as PO in the selection screen allows the user to choose between the Endurance pump running continuously Con or running in the automatic mode Aut such that the pump is energized on...

Page 25: ...ach of the buttons 6 4 5 Oal Minimum Outdoor Reset Point The Oal parameter tells the controller what the minimum allowable supply temperature can be regardless of the outdoor reset calculation For EDP...

Page 26: ...g system T T call for heat Domestic hot water DHW call for heat Error condition detected Supply temperature detected as less than boiler on point 6 6 7 Anti Condense Valve Operation The control on the...

Page 27: ...etween the space in which the appliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appliance not connected to the com...

Page 28: ...en all supply and return valves 2 Fill heating system to minimum operating pressure 12 psig 3 Loosen screw in coin vent and allow any trapped air to escape Collect any water that escapes so that it do...

Page 29: ...l properly If a pump change is required for any reason valve off the boiler and drain approximately 1 or 2 gallons approx 4 8L of water from it Turn off the main disconnect switch and unplug the pump...

Page 30: ...acing shut off the 120 volt power Unplug the transformer wires from the transformer unscrew the two fixing screws and remove the transformer Fit the replacement transformer in reverse order 8 8 PWM Bo...

Page 31: ...om gas valve flange Unplug the blower and the ignitor Remove the bolts from the blower and pull the blower out The boiler assembly may now be removed from the jacket After removal of the boiler assemb...

Page 32: ...WIRING 24V 115V G Y GREEN WITH YELLOW V VIOLET GR GRAY G GREEN O ORANGE BR BROWN BL BLUE Y YELLOW R RED W WHITE BK BLACK COLOUR LEGEND FACTORY WIRING BL W BL W G LINE CONN GND MV1 W S2 FS L2 L1 S1 120...

Page 33: ...durance in setpoint mode instead of outdoor reset mode The ignition control uses LED indication to display the following fault codes Steady On Internal control failure 2 Flashes Erroneous flame signal...

Page 34: ...o disconnect anything to measure the flame current signal To measure the flame signal connect an analog DC microammeter to the FC terminals on the ignition control per Figure 37 The meter should read...

Page 35: ...range adjust the gas valve calibration Always adjust the air orifice first To adjust the gas valve calibration see figure 35 for the location of the offset pressure port and the offset adjustment Whe...

Page 36: ...ct install a smaller gas orifice so that the O2 will rise above 4 or the CO2 will drop to 8 natural or 9 LP The CO2 O2 readings may be influenced by cross contamination Suspect cross contamination if...

Page 37: ...ons of minerals in the water These minerals may cause fouling of the DHW heat exchanger over an extended period of time lime build up Other minerals which react more quickly in well systems mostly mag...