background image

Page 30

LAARS Heating Systems

The control displays the supply temperature, by

default, and the user can access the heat exchanger

inlet temperature, tank temperature (EBP models),

heat exchanger delta T, outdoor air temperature (if

reset is used), and all of the setpoint and differentials

that are set on the boiler. 7 fault codes can also be

displayed, for diagnostic help.

To replace the boiler control, shut off 120V

power to the Endurance. Remove the two sheet metal

screws from the controller mounting bracket. Pull the

controller, attached to the mounting bracket out, to

access the electrical connectors.

Remove the electrical connectors from the

control. Pull out the tabs on the retaining clip, while

pulling the controller out through the front.

Replace in reverse order.

8.5 Ignition Control

The ignition control controls the hot surface

ignitor and proves that the flame signal is appropriate

for powering the gas valve. It also controls the

blower’s pre-purge and post-purge timing. It works

with the boiler control to ensure proper and safe

operation of the Endurance.

To replace the ignition control, shut off the 120-

volt power to the appliance. Remove the cover to the

Endurance control panel. Remove the electrical

connectors from the ignition control. Take out the

controller’s mounting screws, and pull the controller

out. Replace in reverse order.

8.6 Ignitor / Flame Sensor Assembly

The ignitor is a hot surface ceramic composite

device. It is energized whenever there is a call for heat

and switched off when ignition is established.

The flame sensor is a remote sensing flame rod

which is connected directly to the ignition control. The

ignitor should read 50 to 100 ohms resistance when at

room temperature.

If the ignitor fails and the assembly must be

replaced, always install a new ignitor gasket with the

replacement assembly.

For sequence of operation, see Section 9.1,

Servicing.

Caution

Ignitor gets hot.

8.7 Transformer

The control transformer accepts 120 VAC line

voltage and provides 100 VA of 24 VAC control

voltage for the boiler control ONLY. It is NOT

capable of supplying control voltage for external

devices such as zone valves, which MUST have their

own separate power supply.

Should the transformer require replacing, shut off

the 120 volt power. Unplug the transformer wires from

the transformer, unscrew the two fixing screws and

remove the transformer.

Fit the replacement transformer in reverse order.

8.8 PWM Board

The PWM board converts the 0-10V modulating

signal that comes from the boiler control to the PWM

(pulse width modulating) signal that is sent to the

blower to control the blower speed, and hence, the

modulating point of the Endurance.

This board also converts 24V AC to 24V DC,

which is used to power the boiler.

To replace the PWM board, shut off the 120 volt

power. Unplug the two electrical connectors to the

PWM board. Depress the barbs on the four standoffs

to free the board, and pull it out. Replace in reverse

order.

8.9 Blower

The combustion air blower is a high pressure

centrifugal blower. It is powered by a 24VDC motor

which is controlled by the boiler control with voltage

that has been converted by the PWM board. Its speed

will be varied according to the temperature of the

boiler flow.

If a blower change is required, turn off the 120

volt power and unplug the wires from the blower

motor. Remove the four nuts from the blower

discharge flange and the four screws that secure the

gas manifold to the gas valve. Remove the complete

assembly. Unscrew the combustion air inlet assembly

and register plate from the fan.

Fit the replacement fan in reverse order, ensuring

that all joints are made correctly and sealed.

After replacement the combustion should be

checked for correct air fuel ratio (see Section 10).

8.10Transfer Tank (EBP)

The transfer tank contains approximately 20

gallons of boiler water. It functions as an energy

storage vessel to reduce boiler cycling on small output

heating zones and to provide additional heat for

domestic hot water through the domestic hot water

(DHW) plate heat exchanger.

If a tank change is necessary, access to the tank is

possible by removing the jacket’s front door. This is

done by removing the screws that hold the panel at the

top and lifting the panel away. Isolate the appliance

and drain down using the drain cock at the base of the

tank. Remove the tank sensor. Undo the union and the

pump flange bolts that connect the tank to the boiler,

unscrew the panel between the upper and lower

compartments, support the upper components and

remove the tank. Installation of the new tank is done in

the reverse order. After installation purge all air from

the boiler before restarting.

Summary of Contents for EBP0110

Page 1: ...llation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or ope...

Page 2: ...elay 24 6 4 4 Oar Outdoor Reset 24 6 4 5 Oal Minimum Outdoor Reset Point 25 6 4 6 rc Outdoor Reset Ratio 25 6 4 7 oTo Warm Outdoor Shutdown 25 6 4 8 unl Temperature Units 25 6 4 9 Add Control Address...

Page 3: ...with the gas to the burner flame holder Both the intake air and the gas are metered through separate orifices before entering the combustion air blower The blower forces the air fuel mixture through t...

Page 4: ...rain etc during appliance operation or service circulator replacement control replacement etc 1 5 Clearances The dimension and criteria in Table 1 should be followed when choosing the location for the...

Page 5: ...ate the opening centerline 16 1 2 42cm above grade use optional concentric vent terminal extension part number 2400 428 shown in Figure 7 In the U S vent terminals must be at least 3 feet 0 9m above a...

Page 6: ...rements are from the centerlineof the venting to the boiler top or face of outside wall Dimensions shown in inches Configuration 2 Maximum horizontal 38 Maximum vertical 16 Measurements are from the c...

Page 7: ...Endurance Page 7 Figure 7 Concentric Vent Parts Dimensions shown in inches...

Page 8: ...tlet See note 4 3 feet 91 cm J Clearance to nonmechanical air supply Direct Vent Only 12 inches 30 cm inlet to building or the combustion air inlet Other Than Direct Vent 4 feet 1 2 m below or 36 inch...

Page 9: ...atFab Inc under the trade name of Saf T Vent by Z Flex under the trade name of Z Vent and by ProTech Systems Inc under the trade name FasNSeal Follow the special gas vent manufacturer s instructions r...

Page 10: ...Page 10 LAARS Heating Systems Figure 13 3 Vent Parts Dimensions shown in inches...

Page 11: ...r boilers that are getting all of their combustion air from inside the building The confined space shall be provided with two permanent openings communicating directly with other spaces of sufficient...

Page 12: ...reen can be used One portion of this assembly connects to the 5 air collar with a screen for the combustion air and the other part connects to the 3 flue opening see Figure 14 The rest of the 3 vent s...

Page 13: ...ocal requirements 3 Install drip leg ground joint union and drip cap to trap sediment and for test gauge access 4 Support all piping with proper hangers 5 All threaded joints should be coated with pip...

Page 14: ...e domestic potable water temperature has fallen below 39 4 C If this condition is recognized the Endurance pump will run for 5 minutes or until the boiler water temperature reaches 45 F 7 C If the boi...

Page 15: ...Endurance Page 15 Figure 19 Hydronic Piping EDP EBP with Zone Valves Figure 20 Piping Single EDP EBP Boiler for Multiple Temperature Systems Figure 21 Piping Model EDP EDN for Radiant Floor...

Page 16: ...Install an air purger in flow supply line as shown in piping diagrams 5 Install automatic float type air vent on air scoops Figure 22 Hydronic Piping EBP EDP for Systems Zoned with Circulators Figure...

Page 17: ...ipped with a Low Temperature control feature that recognizes when the water temperature at the outlet of the boiler has fallen below 39 F 4 C If this condition is recognized the Endurance pump will ru...

Page 18: ...y hand B BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS D...

Page 19: ...s il n y a pas d odeur de gaz pr s du plancher car le gaz est plus lourd que l air et peut se d poser sur le plancher QUE FAIRE EN CAS D ODEUR DE GAZ N essayez pas d allumer n importe quelque apparei...

Page 20: ...tch Neutral leg to white wire Ground wire can be connected to the grounding screw in the box or on the switch 2 For single zone installations If external pump is required e g because of large system p...

Page 21: ...Clock Thermostats That Require 24 VAC RELAY 24 VOLT NO CONTACT LAARS P N 2400 060 TO T T BOILER CONNECTIONS 120V 24 20VA W Y G R Rc L1 HOT L2 120 VAC TRANSFORMER NOTE This wiring required only for sin...

Page 22: ...rner On Point that is calculated by subtracting the Burner On Differential from the Burner Control Point The Burner On Differential is adjustable from 4 to 30 F 2 to 17 C in the EDP EDN models and is...

Page 23: ...ic Example Figure 32 EDP EDN Flow Schematic 6 Calculated Setpoint for Outdoor Reset shown as CSP when used The temperature that the controller has calculated for a setpoint based on the outdoor temper...

Page 24: ...This parameter shown as PO in the selection screen allows the user to choose between the Endurance pump running continuously Con or running in the automatic mode Aut such that the pump is energized on...

Page 25: ...ach of the buttons 6 4 5 Oal Minimum Outdoor Reset Point The Oal parameter tells the controller what the minimum allowable supply temperature can be regardless of the outdoor reset calculation For EDP...

Page 26: ...g system T T call for heat Domestic hot water DHW call for heat Error condition detected Supply temperature detected as less than boiler on point 6 6 7 Anti Condense Valve Operation The control on the...

Page 27: ...etween the space in which the appliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appliance not connected to the com...

Page 28: ...en all supply and return valves 2 Fill heating system to minimum operating pressure 12 psig 3 Loosen screw in coin vent and allow any trapped air to escape Collect any water that escapes so that it do...

Page 29: ...l properly If a pump change is required for any reason valve off the boiler and drain approximately 1 or 2 gallons approx 4 8L of water from it Turn off the main disconnect switch and unplug the pump...

Page 30: ...acing shut off the 120 volt power Unplug the transformer wires from the transformer unscrew the two fixing screws and remove the transformer Fit the replacement transformer in reverse order 8 8 PWM Bo...

Page 31: ...om gas valve flange Unplug the blower and the ignitor Remove the bolts from the blower and pull the blower out The boiler assembly may now be removed from the jacket After removal of the boiler assemb...

Page 32: ...WIRING 24V 115V G Y GREEN WITH YELLOW V VIOLET GR GRAY G GREEN O ORANGE BR BROWN BL BLUE Y YELLOW R RED W WHITE BK BLACK COLOUR LEGEND FACTORY WIRING BL W BL W G LINE CONN GND MV1 W S2 FS L2 L1 S1 120...

Page 33: ...durance in setpoint mode instead of outdoor reset mode The ignition control uses LED indication to display the following fault codes Steady On Internal control failure 2 Flashes Erroneous flame signal...

Page 34: ...o disconnect anything to measure the flame current signal To measure the flame signal connect an analog DC microammeter to the FC terminals on the ignition control per Figure 37 The meter should read...

Page 35: ...range adjust the gas valve calibration Always adjust the air orifice first To adjust the gas valve calibration see figure 35 for the location of the offset pressure port and the offset adjustment Whe...

Page 36: ...ct install a smaller gas orifice so that the O2 will rise above 4 or the CO2 will drop to 8 natural or 9 LP The CO2 O2 readings may be influenced by cross contamination Suspect cross contamination if...

Page 37: ...ons of minerals in the water These minerals may cause fouling of the DHW heat exchanger over an extended period of time lime build up Other minerals which react more quickly in well systems mostly mag...

Page 38: ...Repair Kit 2400 538 2400 538 16 Anti Condensing Valve Operator Only 2400 539 2400 539 17 Water Flow Switch 2400 542 2400 542 18 Safety Limit 230 F 2400 550 2400 550 2400 550 2400 550 2400 550 2400 55...

Page 39: ...Endurance Page 39...

Page 40: ...x 800 559 1583 Customer Service Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 ww...

Reviews: