background image

Endurance

Page 33

7.

10 seconds after establishing combustion and

proof of flame (via the flame rod signal to

ground), the ignitor will be de-energized.

8.

For EDP/EDN units only, the display should

indicate a rapid rise in temperature to 150º F (1-2

min. duration). During this period the

thermostatic union at the flow outlet is closed

and the boiler is operating in the internal

recirculation mode. [Service note: If the

temperature rise is not rapid the thermostat may

be defective.] At 150° F the thermostat will

allow increased flow to the system.

9.

A gradual rise in temperature will be indicated

until the temperature approaches the Burner

Control Point. The firing rate will modulate

based on the rate of change in temperature as it

seeks the control point.

10. If, during a call for heat, the temperature reaches

the Burner Off Point, the Endurance combustion

will be de-energized, and will allow the

temperature to fall to the Burner On Point before

turning on again.

11. When the call for heat ends on an EDP or EDN

model, the gas valve shuts off, and the pump

post-purge begins, if activated. When the call for

heat ends on an EBP model, the anti-condensing

valve closes, and the Endurance goes into tank

charge mode, until the burner off point

temperature is achieved on the supply sensor.

9.2.1 Fault Code Identification

The boiler control can display the following fault

codes:

F1 = Boiler control internal error

F3 = Gas valve status is on, with no call for

heat

F4 = Supply sensor error

F5 = Tank sensor error (EBP only)

F6 = Return sensor error

F8 = OAT sensor unreliable

LO = Lockout

OFF = Controller is off

ICE = Low temperature protection

The boiler shows an alarm condition by flashing

the code and then showing the supply temperature. All

of the fault conditions shown on the boiler control will

prevent the Endurance from operating, with the

exception of F8. If the outside air temperature sensor

is found by the controller to be unreliable, the

controller will override the outdoor reset function, and

will run the Endurance in setpoint mode, instead of

outdoor reset mode.

The ignition control uses LED indication to

display the following fault codes:

Steady On = Internal control failure

2 Flashes = Erroneous flame signal

3 Flashes = Ignition Control Lockout

9.2.2 Fault Correction

F-1 Switch off boiler and restart. If F-1 repeats,

replace boiler control.

F-3 In normal operation, the ignition control

sends a “gas valve energized” signal to the

boiler control, so the controller will be able

to time its PI algorithms correctly. An F-3

fault code indicates that the ignition control

is sending a signal that the gas valve has

been energized, but there is no call for heat.

The boiler control will not allow the

Endurance to fire in this condition. This

fault indicates that there is either something

mis-wired on the boiler, or that the relay in

this circuit has seized. Check the relay for

seized contacts first, and if the relay is

operational, check the wiring circuit on the

boiler.

F-4 Check for damaged wiring or poor

connection at sensor plug. If they are OK

disconnect the sensor plug and check the

resistance across the sensor terminals. The

resistance of a good sensor is 10,000 ohms

@ 77°F (25°C). Replace sensor if

resistance is less than 500 or more than

20,000 ohms.

F-5 Correct in the same manner as F-4.

F-6 Correct in the same manner as F-4.

F-8 Check that the outdoor air sensor is

installed properly, and that the wire and/or

connection are not damaged. If okay,

disconnect the sensor and check the

resistance across the sensor terminals. The

resistance of a good sensor is 10,000 ohms

at 77°F (25°C). Replace sensor is resistance

is less than 500 or more than 20,000 ohms.

LO See Section 9.2.3
OFF Control power is off. Press and hold the

power button (upper left button) on the

boiler control for 3 seconds to restore

control power. The control will flash “ON”

and then will return to normal operation.

9.2.3 Resolving Lockouts (LO)

There are many causes for lockouts. The six

most common causes are: (a) poor combustion,

(b) poor flame sensor signal, (c) inadequate gas

supply, (d) ignitor failure, (e) blocked or contaminated

air source, (f) safety limit trip. If you get LO on boiler

control, you need to check the ignition control to see if

Summary of Contents for EBP0110

Page 1: ...llation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or ope...

Page 2: ...elay 24 6 4 4 Oar Outdoor Reset 24 6 4 5 Oal Minimum Outdoor Reset Point 25 6 4 6 rc Outdoor Reset Ratio 25 6 4 7 oTo Warm Outdoor Shutdown 25 6 4 8 unl Temperature Units 25 6 4 9 Add Control Address...

Page 3: ...with the gas to the burner flame holder Both the intake air and the gas are metered through separate orifices before entering the combustion air blower The blower forces the air fuel mixture through t...

Page 4: ...rain etc during appliance operation or service circulator replacement control replacement etc 1 5 Clearances The dimension and criteria in Table 1 should be followed when choosing the location for the...

Page 5: ...ate the opening centerline 16 1 2 42cm above grade use optional concentric vent terminal extension part number 2400 428 shown in Figure 7 In the U S vent terminals must be at least 3 feet 0 9m above a...

Page 6: ...rements are from the centerlineof the venting to the boiler top or face of outside wall Dimensions shown in inches Configuration 2 Maximum horizontal 38 Maximum vertical 16 Measurements are from the c...

Page 7: ...Endurance Page 7 Figure 7 Concentric Vent Parts Dimensions shown in inches...

Page 8: ...tlet See note 4 3 feet 91 cm J Clearance to nonmechanical air supply Direct Vent Only 12 inches 30 cm inlet to building or the combustion air inlet Other Than Direct Vent 4 feet 1 2 m below or 36 inch...

Page 9: ...atFab Inc under the trade name of Saf T Vent by Z Flex under the trade name of Z Vent and by ProTech Systems Inc under the trade name FasNSeal Follow the special gas vent manufacturer s instructions r...

Page 10: ...Page 10 LAARS Heating Systems Figure 13 3 Vent Parts Dimensions shown in inches...

Page 11: ...r boilers that are getting all of their combustion air from inside the building The confined space shall be provided with two permanent openings communicating directly with other spaces of sufficient...

Page 12: ...reen can be used One portion of this assembly connects to the 5 air collar with a screen for the combustion air and the other part connects to the 3 flue opening see Figure 14 The rest of the 3 vent s...

Page 13: ...ocal requirements 3 Install drip leg ground joint union and drip cap to trap sediment and for test gauge access 4 Support all piping with proper hangers 5 All threaded joints should be coated with pip...

Page 14: ...e domestic potable water temperature has fallen below 39 4 C If this condition is recognized the Endurance pump will run for 5 minutes or until the boiler water temperature reaches 45 F 7 C If the boi...

Page 15: ...Endurance Page 15 Figure 19 Hydronic Piping EDP EBP with Zone Valves Figure 20 Piping Single EDP EBP Boiler for Multiple Temperature Systems Figure 21 Piping Model EDP EDN for Radiant Floor...

Page 16: ...Install an air purger in flow supply line as shown in piping diagrams 5 Install automatic float type air vent on air scoops Figure 22 Hydronic Piping EBP EDP for Systems Zoned with Circulators Figure...

Page 17: ...ipped with a Low Temperature control feature that recognizes when the water temperature at the outlet of the boiler has fallen below 39 F 4 C If this condition is recognized the Endurance pump will ru...

Page 18: ...y hand B BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS D...

Page 19: ...s il n y a pas d odeur de gaz pr s du plancher car le gaz est plus lourd que l air et peut se d poser sur le plancher QUE FAIRE EN CAS D ODEUR DE GAZ N essayez pas d allumer n importe quelque apparei...

Page 20: ...tch Neutral leg to white wire Ground wire can be connected to the grounding screw in the box or on the switch 2 For single zone installations If external pump is required e g because of large system p...

Page 21: ...Clock Thermostats That Require 24 VAC RELAY 24 VOLT NO CONTACT LAARS P N 2400 060 TO T T BOILER CONNECTIONS 120V 24 20VA W Y G R Rc L1 HOT L2 120 VAC TRANSFORMER NOTE This wiring required only for sin...

Page 22: ...rner On Point that is calculated by subtracting the Burner On Differential from the Burner Control Point The Burner On Differential is adjustable from 4 to 30 F 2 to 17 C in the EDP EDN models and is...

Page 23: ...ic Example Figure 32 EDP EDN Flow Schematic 6 Calculated Setpoint for Outdoor Reset shown as CSP when used The temperature that the controller has calculated for a setpoint based on the outdoor temper...

Page 24: ...This parameter shown as PO in the selection screen allows the user to choose between the Endurance pump running continuously Con or running in the automatic mode Aut such that the pump is energized on...

Page 25: ...ach of the buttons 6 4 5 Oal Minimum Outdoor Reset Point The Oal parameter tells the controller what the minimum allowable supply temperature can be regardless of the outdoor reset calculation For EDP...

Page 26: ...g system T T call for heat Domestic hot water DHW call for heat Error condition detected Supply temperature detected as less than boiler on point 6 6 7 Anti Condense Valve Operation The control on the...

Page 27: ...etween the space in which the appliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appliance not connected to the com...

Page 28: ...en all supply and return valves 2 Fill heating system to minimum operating pressure 12 psig 3 Loosen screw in coin vent and allow any trapped air to escape Collect any water that escapes so that it do...

Page 29: ...l properly If a pump change is required for any reason valve off the boiler and drain approximately 1 or 2 gallons approx 4 8L of water from it Turn off the main disconnect switch and unplug the pump...

Page 30: ...acing shut off the 120 volt power Unplug the transformer wires from the transformer unscrew the two fixing screws and remove the transformer Fit the replacement transformer in reverse order 8 8 PWM Bo...

Page 31: ...om gas valve flange Unplug the blower and the ignitor Remove the bolts from the blower and pull the blower out The boiler assembly may now be removed from the jacket After removal of the boiler assemb...

Page 32: ...WIRING 24V 115V G Y GREEN WITH YELLOW V VIOLET GR GRAY G GREEN O ORANGE BR BROWN BL BLUE Y YELLOW R RED W WHITE BK BLACK COLOUR LEGEND FACTORY WIRING BL W BL W G LINE CONN GND MV1 W S2 FS L2 L1 S1 120...

Page 33: ...durance in setpoint mode instead of outdoor reset mode The ignition control uses LED indication to display the following fault codes Steady On Internal control failure 2 Flashes Erroneous flame signal...

Page 34: ...o disconnect anything to measure the flame current signal To measure the flame signal connect an analog DC microammeter to the FC terminals on the ignition control per Figure 37 The meter should read...

Page 35: ...range adjust the gas valve calibration Always adjust the air orifice first To adjust the gas valve calibration see figure 35 for the location of the offset pressure port and the offset adjustment Whe...

Page 36: ...ct install a smaller gas orifice so that the O2 will rise above 4 or the CO2 will drop to 8 natural or 9 LP The CO2 O2 readings may be influenced by cross contamination Suspect cross contamination if...

Page 37: ...ons of minerals in the water These minerals may cause fouling of the DHW heat exchanger over an extended period of time lime build up Other minerals which react more quickly in well systems mostly mag...

Page 38: ...Repair Kit 2400 538 2400 538 16 Anti Condensing Valve Operator Only 2400 539 2400 539 17 Water Flow Switch 2400 542 2400 542 18 Safety Limit 230 F 2400 550 2400 550 2400 550 2400 550 2400 550 2400 55...

Page 39: ...Endurance Page 39...

Page 40: ...x 800 559 1583 Customer Service Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 ww...

Reviews: