background image

Endurance

Page 11

(21mm per meter). Be sure to take this into

consideration when choosing the vent terminal

location.

For applications requiring vertical venting

through a roof, the same limitations for length and

fittings apply (see Table 2). Vertical vents greater than

7 feet (2.1m) in length must use a condensate trap.

When vertical vent systems have horizontal

components, they must have a condensate drip tee in

the offset. All horizontal portions of the vent system

must slope a minimum 1/4" per foot toward the

condensate drip tee. Laars vertical vent kit and

individual venting components have condensate tees

that work in a vertical vent system, and therefore it is

not necessary to have an offset in a vertical vent

systems that use these parts.

The vertical vent terminal must be placed such

that the bottom of the vent cap is at least 2-feet (0.6m)

above any structure (such as the peak of a roof or

adjacent wall) within 10 feet (3.0m), and must be at

least 3 feet (0.9m) above where the vent pipe exits the

roof (see Figure 12).

Laars offers 3" vent parts for non-concentric

venting, including an in-line condensate tee and vent

caps for vertical venting. See Figure 13 for 3" vent

parts, and Figure 15 for an example of the inline

condensate in a vertical vent system.

IMPORTANT NOTE REGARDING ENDURANCE
VENTING:

 Regardless of the venting arrangement

being used, the flue gas vent material used with the
Endurance MUST be 

stainless steel

 special gas

vent listed to U.L. Standard 1738 and U.L.C.
Standard 636. Endurance flue gases must 

never

 be

vented into a masonry chimney or vented with B-vent
or other galvanized vent material. Endurance units
are 

not

 permitted to be common vented with any

other appliance(s), including other Endurance
appliances.

2.3 Air Source For Combustion

(when not ducted to the Endurance)

When using Category IV venting methods the

appliance draws all combustion air through its top and

from the adjacent space. When locating the appliance

in unconfined spaces in buildings, infiltration may be

adequate to provide air for combustion and

ventilation. However, in buildings of unusually tight

construction, or when locating the appliance in a

confined space, additional air should be provided and

the guidelines below must be followed:

2.3.1 Air From Inside the Building

The following method shall be used to size the

air openings for boilers that are getting all of their

combustion air from inside the building.

The confined space shall be provided with 

two

permanent openings communicating directly with

other spaces of sufficient volume so that the combined

volume of all such spaces meets the criteria for an

unconfined space. The total input of all gas utilization

equipment installed in the combined spaces shall be

used to determine the required minimum volume.

Each

 opening shall have a minimum free area of not

less than 1 in.

2

/1000 Btu/hr (220 mm

2

/kW) of the total

input rating of all gas utilization equipment in the

confined space, but not less than 100 in.

2

 (645 cm

2

).

One opening shall commence within 12 in. (30 cm) of

the top, and one opening shall commence within 12 in.

(30cm) of the bottom, of the enclosure. The minimum

dimension of air openings shall be not less than 3 in.

(8 cm).

2.3.2 All Air From Outdoors

When all air is provided from outdoors, but not

ducted directly to the Endurance, the following

methods shall be used to size the air opening(s).
a.

Two

 permanent openings, one commencing

within 12 in. (30 cm) of the top and one

commencing within 12 in. (30 cm) of the bottom,

of the enclosure shall be provided. The openings

shall communicate directly, or by ducts, with the

outdoors or spaces (crawl or attic) that freely

communicate with the outdoors.
a1. Where directly communicating with the

outdoors or where communicating to the

outdoors through vertical ducts, 

each

opening shall have a minimum free area of

1 in.

2

/4000 Btu/hr (550 mm

2

/kW) of total

input rating of all equipment in the

enclosure.

a2. Where communicating with the outdoors

through horizontal ducts, 

each

 opening

shall have a minimum free area of not less

than 1 in.

2

/2000 Btu/hr (1100 mm

2

/kW) of

total input rating of all equipment in the

enclosure.

b.

One permanent opening, commencing within 12

in. (30 cm) of the top of the enclosure, shall be

permitted where the equipment has clearances of

at least 1 in. (2.5 cm) from the sides and back

and 6 in. (16 cm) from the front of the appliance.

Minimum clearance from
combustibles (vent) U.S.*

3"

8cm

Minimum clearance from
combustibles (vent) Canada

6"

15cm

Max. flue gas temp.

325°F

163°C

Max vent pressure

1.5" w.c.

0.4kPa

Max. equivalent ft. of 3" venting (any

50

15

combination of horizontal or vertical)

equiv. feet

equiv. meters

Max. equivalent ft. of 4" venting (any

100

30

combination of horizontal or vertical)

equiv. feet

equiv. meters

*Note: To use 3" (8cm) clearance, the vent must be open on at
least one side. If fully enclosed, clearance is 6" (15cm)

Table 2. Category IV Vent Parameters.

Summary of Contents for EBP0110

Page 1: ...llation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or ope...

Page 2: ...elay 24 6 4 4 Oar Outdoor Reset 24 6 4 5 Oal Minimum Outdoor Reset Point 25 6 4 6 rc Outdoor Reset Ratio 25 6 4 7 oTo Warm Outdoor Shutdown 25 6 4 8 unl Temperature Units 25 6 4 9 Add Control Address...

Page 3: ...with the gas to the burner flame holder Both the intake air and the gas are metered through separate orifices before entering the combustion air blower The blower forces the air fuel mixture through t...

Page 4: ...rain etc during appliance operation or service circulator replacement control replacement etc 1 5 Clearances The dimension and criteria in Table 1 should be followed when choosing the location for the...

Page 5: ...ate the opening centerline 16 1 2 42cm above grade use optional concentric vent terminal extension part number 2400 428 shown in Figure 7 In the U S vent terminals must be at least 3 feet 0 9m above a...

Page 6: ...rements are from the centerlineof the venting to the boiler top or face of outside wall Dimensions shown in inches Configuration 2 Maximum horizontal 38 Maximum vertical 16 Measurements are from the c...

Page 7: ...Endurance Page 7 Figure 7 Concentric Vent Parts Dimensions shown in inches...

Page 8: ...tlet See note 4 3 feet 91 cm J Clearance to nonmechanical air supply Direct Vent Only 12 inches 30 cm inlet to building or the combustion air inlet Other Than Direct Vent 4 feet 1 2 m below or 36 inch...

Page 9: ...atFab Inc under the trade name of Saf T Vent by Z Flex under the trade name of Z Vent and by ProTech Systems Inc under the trade name FasNSeal Follow the special gas vent manufacturer s instructions r...

Page 10: ...Page 10 LAARS Heating Systems Figure 13 3 Vent Parts Dimensions shown in inches...

Page 11: ...r boilers that are getting all of their combustion air from inside the building The confined space shall be provided with two permanent openings communicating directly with other spaces of sufficient...

Page 12: ...reen can be used One portion of this assembly connects to the 5 air collar with a screen for the combustion air and the other part connects to the 3 flue opening see Figure 14 The rest of the 3 vent s...

Page 13: ...ocal requirements 3 Install drip leg ground joint union and drip cap to trap sediment and for test gauge access 4 Support all piping with proper hangers 5 All threaded joints should be coated with pip...

Page 14: ...e domestic potable water temperature has fallen below 39 4 C If this condition is recognized the Endurance pump will run for 5 minutes or until the boiler water temperature reaches 45 F 7 C If the boi...

Page 15: ...Endurance Page 15 Figure 19 Hydronic Piping EDP EBP with Zone Valves Figure 20 Piping Single EDP EBP Boiler for Multiple Temperature Systems Figure 21 Piping Model EDP EDN for Radiant Floor...

Page 16: ...Install an air purger in flow supply line as shown in piping diagrams 5 Install automatic float type air vent on air scoops Figure 22 Hydronic Piping EBP EDP for Systems Zoned with Circulators Figure...

Page 17: ...ipped with a Low Temperature control feature that recognizes when the water temperature at the outlet of the boiler has fallen below 39 F 4 C If this condition is recognized the Endurance pump will ru...

Page 18: ...y hand B BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS D...

Page 19: ...s il n y a pas d odeur de gaz pr s du plancher car le gaz est plus lourd que l air et peut se d poser sur le plancher QUE FAIRE EN CAS D ODEUR DE GAZ N essayez pas d allumer n importe quelque apparei...

Page 20: ...tch Neutral leg to white wire Ground wire can be connected to the grounding screw in the box or on the switch 2 For single zone installations If external pump is required e g because of large system p...

Page 21: ...Clock Thermostats That Require 24 VAC RELAY 24 VOLT NO CONTACT LAARS P N 2400 060 TO T T BOILER CONNECTIONS 120V 24 20VA W Y G R Rc L1 HOT L2 120 VAC TRANSFORMER NOTE This wiring required only for sin...

Page 22: ...rner On Point that is calculated by subtracting the Burner On Differential from the Burner Control Point The Burner On Differential is adjustable from 4 to 30 F 2 to 17 C in the EDP EDN models and is...

Page 23: ...ic Example Figure 32 EDP EDN Flow Schematic 6 Calculated Setpoint for Outdoor Reset shown as CSP when used The temperature that the controller has calculated for a setpoint based on the outdoor temper...

Page 24: ...This parameter shown as PO in the selection screen allows the user to choose between the Endurance pump running continuously Con or running in the automatic mode Aut such that the pump is energized on...

Page 25: ...ach of the buttons 6 4 5 Oal Minimum Outdoor Reset Point The Oal parameter tells the controller what the minimum allowable supply temperature can be regardless of the outdoor reset calculation For EDP...

Page 26: ...g system T T call for heat Domestic hot water DHW call for heat Error condition detected Supply temperature detected as less than boiler on point 6 6 7 Anti Condense Valve Operation The control on the...

Page 27: ...etween the space in which the appliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appliance not connected to the com...

Page 28: ...en all supply and return valves 2 Fill heating system to minimum operating pressure 12 psig 3 Loosen screw in coin vent and allow any trapped air to escape Collect any water that escapes so that it do...

Page 29: ...l properly If a pump change is required for any reason valve off the boiler and drain approximately 1 or 2 gallons approx 4 8L of water from it Turn off the main disconnect switch and unplug the pump...

Page 30: ...acing shut off the 120 volt power Unplug the transformer wires from the transformer unscrew the two fixing screws and remove the transformer Fit the replacement transformer in reverse order 8 8 PWM Bo...

Page 31: ...om gas valve flange Unplug the blower and the ignitor Remove the bolts from the blower and pull the blower out The boiler assembly may now be removed from the jacket After removal of the boiler assemb...

Page 32: ...WIRING 24V 115V G Y GREEN WITH YELLOW V VIOLET GR GRAY G GREEN O ORANGE BR BROWN BL BLUE Y YELLOW R RED W WHITE BK BLACK COLOUR LEGEND FACTORY WIRING BL W BL W G LINE CONN GND MV1 W S2 FS L2 L1 S1 120...

Page 33: ...durance in setpoint mode instead of outdoor reset mode The ignition control uses LED indication to display the following fault codes Steady On Internal control failure 2 Flashes Erroneous flame signal...

Page 34: ...o disconnect anything to measure the flame current signal To measure the flame signal connect an analog DC microammeter to the FC terminals on the ignition control per Figure 37 The meter should read...

Page 35: ...range adjust the gas valve calibration Always adjust the air orifice first To adjust the gas valve calibration see figure 35 for the location of the offset pressure port and the offset adjustment Whe...

Page 36: ...ct install a smaller gas orifice so that the O2 will rise above 4 or the CO2 will drop to 8 natural or 9 LP The CO2 O2 readings may be influenced by cross contamination Suspect cross contamination if...

Page 37: ...ons of minerals in the water These minerals may cause fouling of the DHW heat exchanger over an extended period of time lime build up Other minerals which react more quickly in well systems mostly mag...

Page 38: ...Repair Kit 2400 538 2400 538 16 Anti Condensing Valve Operator Only 2400 539 2400 539 17 Water Flow Switch 2400 542 2400 542 18 Safety Limit 230 F 2400 550 2400 550 2400 550 2400 550 2400 550 2400 55...

Page 39: ...Endurance Page 39...

Page 40: ...x 800 559 1583 Customer Service Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 ww...

Reviews: