4
Item
DCPS
Input system
110 V AC dual–live wire
AC input
Four terminals (for one to four routes)
DC output circuit breaker
16 BLVD circuit breakers (1 A to 100 A, depending on
customer requirements)
BLVD is short for battery low voltage disconnection.
DC surge protection
Differential mode: 10 kA; common mode: 20 kA
Battery circuit breaker
Two circuit breakers (A maximum of 200 A, depending on
customer requirements)
Table 2 – Power Distribution Specifications
2.3 Rectifier
Appearance
Rectifiers convert AC input into stable 48 V DC output.
Figure 5 – Rectifier
Panel
Figure 6 – Rectifier Panel
(1) Power indicator
(2) Alarm indicator
(3) Fault indicator
(4) Locking latch
(5) Handle