3 Installation
3.1 Installation
Preparations
3.1.1. Tools
Figure 12 – Installation Tools
3.1.2 Requirements for Cable Routing
The bending semidiameter of power cables and ground cables should be greater than or
equal to three times the diameter of the power cables and ground cables respectively.
The bending semidiameter of signal cables should be greater than or equal to five times
the diameter of the signal cables.
Cables of the same type should be bound together. Cables of different types should
keep a minimum distance of 30 mm from each other to avoid tangles.
Cables that are bound together should be close to each other, neat, and free of
damage.
The protection ground cables must not be bound to or tangled with the signal cables.
An appropriate distance should be left between them to minimize interruption.
AC power cables, DC power cables, signal cables, and communications cables must be
bound separately.
Power cables must be routed straightly. No joint or weld can be found in a power cable.
In case of insufficient cable length, use a longer cable.