28
Figure 34 – Setting SNMPv3 parameters
Step 7
Set the Trap Target Address and Trap Port.
Step 8
Export the Mib file and import it to the EMS.
5.7
Connecting the Battery Supply
Prerequisites
CAUTION:
To avoid damage to batteries, switch on the battery circuit breaker only after you correctly set the
battery parameters.
Procedure
Step 1
Switch off the upper-level circuit breaker.
Step 2
Switch on the battery circuit breaker.
Step 3
Switch on the upper-level circuit breaker.
Step 4
Switch all the circuit breakers to appropriate status based on site requirements.
Step 5
Observe the DCPS for 15 minutes. If no alarm is generated on the LCD of the DCSC during
Step 6
this period of time, the voltages and currents for batteries and loads are normal.