KEW6305
4.6
“
Setting 04” Current range
Selectable Current range differs by clamp sensor selected at “
Setting 03
”.
Clamp sensor (“Setting 03”)
Current range
50A (M-8128)
1 / 5 / 10 / 25 / 50A / AUTO
100A (M-8127)
2 / 10 / 20 / 50 / 100A / AUTO
200A (M-8126)
4 / 20 / 40 / 100 / 200A / AUTO
500A (M-8125)
10 / 50 / 100 / 250 / 500A / AUTO
1000A (M-8124)
20 / 100 / 200 / 500 / 1000A / AUTO
3000A
300 / 1000 / 3000A
Default value (or after system reset)
AUTO
* Selecting “AUTO” activates auto-ranging function and the measuring range will be automatically
switched between the lowest and highest ranges.
1 Use the
Cursor
key on the selection screen, and select “Setting 04”.
2 Press the
ENTER
key to get the instrument into setting change mode.
3 Present setting (or default value: AUTO) blinks. Select the appropriate current range with the
Cursor
key, and then press the
ENTER
key after making necessary change.
NOTE:
* When a type of clamp sensor (“Setting 04”) is changed, current range may be changed to the
corresponding range automatically.
* Accurate results may not be obtained if the Clamp sensors in use do not match the setting done for
sensor.
* Using the auto-ranging function can measure wide range of input signals, however, accurate results
may not be obtained when measuring loads that flactuate so widely within 1 sec..