KEW6305
4.4
“
Setting 02” Voltage rang
Selecting a measurement range so that the estimated inputs will be close to the full scale value is
recommended to obtain accurate results. Recommended range selections are: 150V range for rated
voltages between 100 - 120V, 300V range for 200 - 240V and 600V range for 400 – 440V.
Setting item
150V / 300V / 600V
Default value (or after system reset)
300V
1 Use the
Cursor
key on the selection screen, and select “Setting 02”.
2 Press the
ENTER
key to get the instrument into setting change mode.
3 Present setting (or default value: 300V) blinks. Select the appropriate voltage range with the
Cursor
key, and then press the
ENTER
key after making necessary change.