4.5
KEW6305
“
Setting 03” Clamp sensor
Selectable Current range (“
Setting 04
”) differs by the selected Clamp sensors.
Clamp sensor
Current range (” Setting 04 ”)
50A (M-8128)
1 / 5 / 10 / 25 / 50A / AUTO
100A (M-8127)
2 / 10 / 20 / 50 / 100A / AUTO
200A (M-8126)
4 / 20 / 40 / 100 / 200A / AUTO
500A (M-8125)
10 / 50 / 100 / 250 / 500A / AUTO
1000A (M-8124)
20 / 100 / 200 / 500 / 1000A / AUTO
3000A
300 / 1000 / 3000A
Default value (or after system reset)
500A
1 Use the
Cursor
key on the selection screen, and select “Setting 03”.
2 Press the
ENTER
key to get the instrument into setting change mode.
3 Present setting (or default value: 500A) blinks. Select the appropriate clamp sensor with the
Cursor
key, and then press the
ENTER
key after making necessary change.
NOTE:
* Accurate results may not be obtained if the Clamp sensors in use do not match the setting
done for sensor.