22
Battery input
connector
Crimped OT
terminals
M12
13.5mm
35N
•
m
Output
connector
Crimped OT
terminals
M12
13.5mm
35N
•
m
Grounding
connector
Crimped OT
terminals
M12
13.5mm
35N
•
m
1200k
Mains input
connector
Crimped OT
terminals
M12
13.5mm
35N
•
m
Bypass input
connector
Crimped OT
terminals
M12
13.5mm
35N
•
m
Battery input
connector
Crimped OT
terminals
M12
13.5mm
35N
•
m
Output
connector
Crimped OT
terminals
M12
13.5mm
35N
•
m
Grounding
connector
Crimped OT
terminals
M12
13.5mm
35N
•
m
3.6.3
Recommended input front-end and output back-end circuit breakers
UPS capacity
Component
Specifications
100k
Mains input circuit breaker
200A
3P
Bypass input circuit breaker
200A
3P
Output circuit breaker r
200A
3P
Battery circuit breaker
320A
3P
120k
Mains input circuit breaker
250A
3P
Bypass input circuit breaker
250A
3P
Output circuit breaker
250A
3P
Battery circuit breaker
400A
3P
150K&160k
Mains input circuit breaker
320A
3P
Bypass input circuit breaker
320A
3P
Output circuit breaker
320A
3P
Battery circuit breaker
500A
3P
200k
Mains input circuit breaker
400A
3P
Bypass input circuit breaker
400A
3P
Output circuit breaker
400A
3P
Battery circuit breaker
630A
3P
250k
Mains input circuit breaker
500A
3P
Bypass input circuit breaker
500A
3P
Output circuit breaker
500A
3P
Battery circuit breaker
800A
3P
300k
Mains input circuit breaker
500A
3P
Bypass input circuit breaker
500A
3P
Summary of Contents for HIP3300E
Page 14: ...13 Side View Rear View Full configuration...
Page 15: ...14 Connect coppper bar Mains bypass common copper bar...
Page 29: ...28 3 9 3 UPS installation The whole systems are showed below 4 Operation 4 1 Operation Modes...
Page 40: ...39...
Page 41: ...40 4 3 3 Alarm View the alarm and history of the UPS and open or close the buzer...
Page 49: ...48...
Page 59: ...58 4 3 5 1 USB Wizard History Output download history and setting record by USB...