67
Network Management Card replacement
SNMP card: internal SNMP / external SNMP optional
◆
Loosen the 2 torque screws (on each side of the card)
.
◆
Carefully pull out the card. Reverse the procedure for re-installation
The slot called SNMP supports the MEGAtec protocol. We advise that NetAgent II-3 port is
also a tool to remotely monitor and manage any UPS system
The overview of the SNMP card
NetAgent II-3Ports supports the Modem Dial-in (PPP) function to enable the remote control
via the internet when the network is unavailable.
In addition to the features of a standard NetAgent Mini, NetAgent II has the option to add
NetFeeler Lite to detect temperature, humidity, smoke and security sensors. Thus, making
NetAgent II a versatile management tool. NetAgent II also supports multiple languages and is
setup for web-based auto language detection.
Typical topology of the UPS Network Management
Appendix 1 Specifications
Model
100kVA
120kVA
150kVA
160kVA
Cabinet capacity
(VA/W)
100k / 100k
120k / 120k
150k / 150k
160k / 160k
Input
Phase
3 Phase 4 Wires and Ground
Rated Voltage
380/400/415Vac
Voltage Range
138~485Vac
◆
At 40°C: The UPS works at full load when the voltage is
323–485Vac and is derated load when the
voltage is 323–138Vac
◆
At 30°C: The UPS works at full load when the voltage is
305–485Vac and is derated load when the
voltage is 305–138Vac
Frequency Range
40Hz-70Hz
Power Factor
≥0.99
Current THDi
≤3%(100% nonlinear load)
Bypass Voltage
Range
Max.voltage: 220V:+25 %( op10%, +15%, +20%);
230V:+20 %( op10%, +15%);
240V:+15 %( op10%);
Min. voltage:-45 %( optional -10%, -20%,-30%)
Summary of Contents for HIP3300E
Page 14: ...13 Side View Rear View Full configuration...
Page 15: ...14 Connect coppper bar Mains bypass common copper bar...
Page 29: ...28 3 9 3 UPS installation The whole systems are showed below 4 Operation 4 1 Operation Modes...
Page 40: ...39...
Page 41: ...40 4 3 3 Alarm View the alarm and history of the UPS and open or close the buzer...
Page 49: ...48...
Page 59: ...58 4 3 5 1 USB Wizard History Output download history and setting record by USB...
Page 60: ...59 4 3 5 1 1 Alarm Log Output 4 3 5 1 2 Setting Log Output...