23
Output circuit breaker
500A
3P
Battery circuit breaker
1000A
3P
400k
Mains input circuit breaker
800A
3P
Bypass input circuit breaker
630A
3P
Output circuit breaker
630A
3P
Battery circuit breaker
1250A
3P
500k
Mains input circuit breaker
1000A
3P
Bypass input circuit breaker
800A
3P
Output circuit breaker
800A
3P
Battery circuit breaker
1600A
3P
600k
Mains input circuit breaker
1250A
3P
Bypass input circuit breaker
1000A
3P
Output circuit breaker
1000A
3P
Battery circuit breaker
2000A
3P
800k
Mains input circuit breaker
1600A
3P
Bypass input circuit breaker
1250A
3P
Output circuit breaker
1250A
3P
Battery circuit breaker
2500A
3P
1000k
Mains input circuit breaker
2000A
3P
Bypass input circuit breaker
1600A
3P
Output circuit breaker
1600A
3P
Battery circuit breaker
3200A
3P
1200k
Mains input circuit breaker
2500A
3P
Bypass input circuit breaker
2000A
3P
Output circuit breaker
2000A
3P
Battery circuit breaker
4000A
3P
CAUTION!
Protective earth cable: Connect each cabinet to the main ground system. For
Grounding connection, follow the shortest route possible.
WARNING!
FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES MAY
RESULT IN ELECTROMAGNETIC INTERFERENCE OR IN HAZARDS
INVOLVING ELECTRIC SHOCK AND FIRE
3.6 Power cable connect
Before equipment has been installed, must comfirm the input source type, common input or Split
input, if the input source is dual input, must remove the copper bar that connected bypass and mains.
Summary of Contents for HIP3300E
Page 14: ...13 Side View Rear View Full configuration...
Page 15: ...14 Connect coppper bar Mains bypass common copper bar...
Page 29: ...28 3 9 3 UPS installation The whole systems are showed below 4 Operation 4 1 Operation Modes...
Page 40: ...39...
Page 41: ...40 4 3 3 Alarm View the alarm and history of the UPS and open or close the buzer...
Page 49: ...48...
Page 59: ...58 4 3 5 1 USB Wizard History Output download history and setting record by USB...
Page 60: ...59 4 3 5 1 1 Alarm Log Output 4 3 5 1 2 Setting Log Output...